7.4 List of Periodic Replacement Parts
7-5
M
AI
N
TEN
AN
C
E A
N
D
IN
S
P
EC
TI
O
N
Chap
7
7.4 List of Periodic Replacement Parts
Each part of the inverter has its own service life that will vary according to the environmental and operating
conditions. It is recommended that the following parts be replaced at the specified intervals.
When the replacement is necessary, consult your Fuji Electric representative.
Table 7.4-1 Replacement Parts
Part name
Standard replacement intervals
(See
Note
below.)
DC link bus capacitor
10 years (7 years in the ND mode)
Electrolytic capacitors on printed circuit boards
10 years (7 years in the ND mode)
Cooling fans
10 years (7 years in the ND mode)
Fuses
10 years (7 years in the ND mode)
Note.
These replacement intervals are based on the inverter’s service life estimated at a surrounding temperature
of 40°C at 100% (HHD-mode inverters) or 80% (ND-/HD-/HND-mode inverters) of full load. In environments
with an ambient temperature above 40°C or a large amount of dust or dirt, the replacement intervals may be
shorter. The condition for inverters of FRN0020E2
■
-2
/FRN0012E2
■
-4
/FRN0011E2
■
-7
or below
capacity models is a load ratio of 80% even for HHD-mode.
Notes for periodic replacement of parts
(1) The replacement intervals listed above are a guide for almost preventing parts from failure if those parts are
replaced with new ones at the intervals. They do not guarantee the completely fault-free operation.
(2) Table 7.4-1 does not apply to unused spare parts being kept in storage.
It applies only when they are stored under the temporary and long-term storage conditions given in Chapter 1
“1.3.2 Storage environment” and energized approximately once a year.
(3) Cooling fans can be replaced by users. As for other parts, only the persons who have finished the Fuji Electric
training course can replace them. For the purchase of spare cooling fans and the request for replacement of
other parts, contact the sales agent where you purchased the product or your nearest Fuji Electric
representative.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......