5.2 Function Codes Table
5-39
FU
NCT
IO
N
C
O
DE
S
Chap 5
■
3-phase 400V class, Fuji standard motor
Motor rated
capacity setting
range (kW)
P02/A16
Applicable
motor
capacity
(kW)
Rated
current
(A)
P03/A17
*1
No-load
current
(A)
P06/A20
*1
%R1 (%)
P07/A21
*1
%X (%)
P08/A22
*1
Rated slip
frequency
P12/A26
Iron loss
factor 1
P13/A27
Starting
mode (Auto
search delay
time 2)
H46
0.01 to 0.09
0.06
0.22
0.20
13.79
11.75
1.77
14.00
0.5
0.10 to 0.19
0.1
0.35
0.27
12.96
12.67
1.77
14.00
0.20 to 0.39
0.2
0.65
0.53
12.95
12.92
2.33
12.60
0.40 to 0.74
0.4
1.15
0.83
10.20
13.66
2.40
9.88
0.75 to 1.49
0.75
1.80
1.15
8.67
10.76
2.33
7.40
1.50 to 2.19
1.5
3.10
1.51
6.55
11.21
2.00
5.85
2.20 to 3.69
2.2
4.60
2.43
6.48
10.97
1.80
5.91
0.6
3.70 to 5.49
3.7
7.50
3.84
5.79
11.25
1.93
5.24
0.8
5.50 to 7.49
5.5
11.50
5.50
5.28
14.31
1.40
4.75
1.0
7.50 to 10.99
7.5
14.50
6.25
4.50
14.68
1.57
4.03
1.2
11.00 to 14.99
11
21.00
8.85
3.78
15.09
1.07
3.92
1.3
15.00 to 18.49
15
27.50
10.00
3.25
16.37
1.13
3.32
2.0
18.50 to 21.99
18.5
34.00
10.70
2.92
16.58
0.87
3.34
22.00 to 29.99
22
39.00
12.60
2.70
16.00
0.90
3.28
30.00 to 36.99
30
54.00
19.50
2.64
14.96
0.80
3.10
2.3
37.00 to 44.99
37
65.00
20.80
2.76
16.41
0.80
2.30
2.5
45.00 to 54.99
45
78.00
23.80
2.53
16.16
0.80
2.18
55.00 to 74.99
55
95.00
29.30
2.35
16.20
0.94
2.45
2.6
75.00 to 89.99
75
130.0
41.60
1.98
16.89
0.80
2.33
2.8
90.00 to 109.9
90
155.0
49.60
1.73
16.03
0.80
2.31
3.2
110.0 to 131.9
110
188.0
45.60
1.99
20.86
0.66
1.73
3.5
132.0 to 159.9
132
224.0
57.60
1.75
18.90
0.66
1.80
4.1
160.0 to 199.9
160
272.0
64.50
1.68
19.73
0.66
1.50
4.5
200.0 to 219.9
200
335.0
71.50
1.57
20.02
0.66
1.36
4.7
220.0 to 249.9
220
365.0
71.80
1.60
20.90
0.58
1.25
250.0 to 279.9
250
415.0
87.90
1.39
18.88
0.54
1.33
5.0
280.0 to 314.9
280
462.0
93.70
1.36
19.18
1.27
5.5
315.0 to 354.9
315
520.0
120.0
0.84
16.68
0.45
1.81
5.6
355.0 to 399.9
355
580.0
132.0
0.83
16.40
0.43
1.77
400.0 to 449.9
400
670.0
200.0
0.62
15.67
0.29
1.58
7.5
450.0 to 499.9
450
770.0
270.0
0.48
13.03
0.23
1.84
9.8
500.0 to 559.9
500
835.0
0.51
12.38
0.18
1.80
560.0 to 629.9
560
940.0
0.57
13.94
0.20
1.61
630.0 to 709.9
630
1050.0
355.0
0.46
11.77
0.17
1.29
10.5
710.0 or above 710
1150.0
290.0
0.54
14.62
0.21
0.97
*1: F05: The value for the model, in which the rated voltage at base frequency 1 is not 400V, becomes the
optimal value, which is different from the above value.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......