5.3 Description of Function Codes
5-81
FU
NCT
IO
N
C
O
DE
S
Chap 5
■
Motor Sound (Tone) (F27)
F27 changes the motor running sound tone (only for motors under V/f control). This setting is effective when the
carrier frequency specified by function code F26 is 7 kHz or lower. Changing the tone level may reduce the high
and harsh running noise from the motor.
If the tone level is set too high, the output current may become unstable, or mechanical vibration and
noise may increase. Also, this function code may not be very effective for certain types of motor.
F27 data
Function
0
Disable (Level 0)
1
Enable (Level 1)
2
Enable (Level 2)
3
Enable (Level 3)
F29 to F35 Terminal [FM], [FM2] (Mode selection, Output gain, Function selection, Pulse rate)
These function codes allow outputting monitor data such as output frequency and output current to terminals [FM],
[FM2] as analog DC voltage, current, and pulse ([FM] only). In addition, voltage and current output level on
terminals [FM], [FM2] is adjustable.
When switching voltage, current, and pulse, it is necessary to switch both mode selection function code
and switch on the PCB.
Terminal [FM2] is mounted only on GB specification and C specification (for China).
There is no pulse output function for terminal [FM2]
Terminal
Mode selection function
Gain
Function
Pulse rate
Switch
[FM]
F29
F30
F31
F33
SW5
[FM2]
F32
F34
F35
None
SW7
■
Mode selection (F29, F32)
F29 and F32 select output form of terminals [FM], [FM2]. Accordingly ,change the switches SW5, SW7 on the
control PCB.
For details of the switches on the control PCB, refer to Chapter 12 “SPECIFICATIONS.”
F29 data
Terminal [FM] output form
Control PCB switch (SW5)
0
Voltage output (0 to +10 VDC)
FMV side
1
Current output (4 to 20 mA DC)
FMI side
2
Current output (0 to 20mA DC)
3
Pulse output
FMP side
F32 data
Terminal [FM2] Output form
Control PCB switch (SW7)
0
Voltage output (0 to +10 VDC)
FMV side
1
Current output (4 to 20 mA DC)
FMI side
2
Current output (0 to 20mA DC)
The output current is not isolated from analog input, and does not have an isolated power supply.
Therefore, if an electrical potential relationship between the inverter and peripheral equipment has been
established, e.g., by connecting an analog input, cascade connection of a current output device is not
available.
Keep the optimum connection wire length.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......