![Fuji Electric FRENIC-Ace series User Manual Download Page 218](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846218.webp)
5.3 Description of Function Codes
5-48
[ 2 ] Setting up a reference frequency using analog input (F01 = 1 to 3, 5)
It is possible to arbitrarily specify a frequency setting from the analog inputs (voltage value to be input to terminal
[12] or terminal [C1] (V2 function) or current value to be input to terminal [C1] (C1 function)) by multiplying them
with the gain and adding the bias. The polarity can be selected and the filter time constant and offset can be
adjusted.
Adjustment constants of frequency setting 1
F01
data
Input terminal
Input range
Bias
Gain
Polarity
selection Filter
Offset
Bias
Base
point
Gain
Base
point
1
[12]
0 to +10V,
-10 to +10V
F18
C50
C32
C34
C35
C33
C31
2
[C1] (C1 function) 4 to 20 mA
0 to 20 mA
F18
C50
C37
C39
C40
C38
C36
3
[12]+ [C1]
(C1 function)
(Set by result of
addition)
0 to +10V,
-10 to +10V
F18
C50
C32
C34
C35
C33
C31
4 to 20 mA
0 to 20 mA
F18
C50
C37
C39
C40
C38
C36
5
[C1] (V2 function)
0 to +10V
F18
C50
C42
C44
C45
C43
C41
Adjustment constants of frequency setting 2
C30
data
Input terminal
Input range
Bias
Gain
Polarity
selection Filter
Offset
Bias
Base
point
Gain
Base
point
1
[12]
0 to +10V,
-10 to +10V
C55
C56
C32
C34
C35
C33
C31
2
[C1] (C1 function) 4 to 20 mA
0 to 20 mA
C61
C62
C37
C39
C40
C38
C36
3
[12]+
[C1] (C1 function)
(Set by result of
addition)
0 to +10V,
-10 to +10V
C55
C56
C32
C34
C35
C33
C31
4 to 20 mA
0 to 20 mA
C61
C62
C37
C39
C40
C38
C36
5
[C1] (V2 function)
0 to +10V
C67
C68
C42
C44
C45
C43
C41
■
Offset (C31, C36, C41)
C31, C36 or C41 configures an offset for an analog voltage/current input. The offset also applies to signals sent
from the external equipment.
■
Filter (C33, C38, C43)
C33, C38, and C43 provide the filter time constants for the voltage and current of the analog input. The larger the
time constant, the slower the response. Specify the proper filter time constant taking into account the response
speed of the machine (load). If the input voltage fluctuates due to line noises, increase the time constant.
■
Terminal [12] Polarity selection (C35)
C35 configures the polarity and therefore the input range for analog input voltage.
C35 data
Modes for terminal inputs
0
-10 to +10 V
1
0 to +10 V (Negative value of voltage is regarded as 0 V)
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......