11.3 Molded Case Circuit Breaker (MCCB), Residual-current-operated Protective Device
(RCD)/Earth Leakage Circuit Breaker (ELCB) and Magnetic Contactor (MC)
11-14
Table 11.3-2 lists the relationship between the rated leakage current sensitivity of RCDs/ELCBs (with overcurrent
protection) and wiring length of the inverter output circuits. Note that the sensitivity levels listed in the table are
estimated values based on the results obtained by the test setup in the Fuji laboratory where each inverter drives a
single motor.
Table 11.3-2 Rated Current Sensitivity of Residual-Current-Operated Protective Device (RCD)/ Earth Leakage
Circuit Breakers (ELCBs)
Voltage class
Nominal applied
motor
(kW) [HP]
Wiring length and current sensitivity
10m (33ft)
30m (98ft)
50m (164ft)
100m (328ft)
200m (656ft)
300m (984ft)
Three-phase
200V class
0.1 [1/8]
0.2 [1/4]
0.4 [1/2]
0.75 [1]
1.5 [2]
2.2 [3]
30mA
3.7 [5]
5.5 [7.5]
7.5 [10]
100mA
11 [15]
15 [20]
18.5 [25]
200mA
22 [30]
30 [40]
37 [50]
45 [60]
55 [75]
75 [100]
500mA
90 [125]
110 [150]
Three-phase
400V class
0.4 [1/2]
0.75 [1]
1.5 [2]
2.2 [3]
3.7 [5]
30mA
5.5 [7.5]
7.5 [10]
11 [15]
15 [20]
18.5 [25]
22 [30]
30 [40]
100mA
37 [50]
200mA
45 [60]
55 [75]
500mA
75 [100]
90 [125]
1000mA
110 [150]
132 [200]
160 [250]
200 [300]
220 [350]
250 [400]
280 [450]
315 [475]
3000mA
355 [500]
400 [600]
450 [700]
500 [800]
630 [900]
•
Values listed above were obtained using Fuji ELCB EG or SG series applied to the test setup.
•
The rated current of applicable motor rating indicates values for Fuji standard motor (4 poles, 50 Hz and 200 V
three-phase).
•
The leakage current is calculated based on neutral grounding for 400 V class Y-connection power lines.
•
Values listed above are calculated based on the static capacitance to the earth when the 600 V class of
vinyl-insulated IV wires are used in a wiring through metal conduit pipes.
•
Wiring length is the total length of wiring between the inverter and motor. If more than one motor is to be
connected to a single inverter, the wiring length should be the total length of wiring between the inverter and
motors.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......