12.1 Standard Model
12-16
■
Standard-model, Three-phase 400 V (460 V) class series (HHD-mode: 45 kW to 220 kW)
Item
Specifications
Type (FRN_ _ _ _E2S-4
)
0139
0168
0203
0240
0290
0361
0415
0520
0590
Nominal applied motor (kW) [HP]
(Output rating)
*1
45
[60]
55
[75]
75
[100]
90
[125]
110
[150]
132
[200]
160
[250]
200
[300]
220
[350]
O
utput r
ati
ngs
Rated capacity (kVA)
*2
69
[73]
85
[89]
114
[120]
134
[140]
160
[167]
193
[202]
232
[242]
287
[300]
316
[331]
Rated voltage (V)
*
3
Three-phase 380 to 480 V (with AVR function)
Rated current (A)
*
4
91
112
150
176
210
253
304
377
415
Overload capability
150%-1 min, 200%-0.5 s
Input powe
r
Voltage, frequency
Three-phase 380
to 480 V, 50/60 Hz
Three-phase 380 to 440 V, 50 Hz
Three-phase 380 to 480 V, 60 Hz
*5
Allowable voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*6
,
Frequency: +5 to -5%
Rated input current
*7
(w/o DCR) (A)
114
140
–
–
–
–
–
–
–
(with DCR) (A)
83.2
102
138
164
201
238
286
357
390
Required capacity
(with DCR) (kVA)
*8
58
71
96
114
140
165
199
248
271
B
rak
ing
Torque (%)
*9
10% to 15%
DC braking
Braking starting frequency: 0.0 to 60.0 Hz, Braking time: 0.0 to 30.0 s,
Braking level: 0 to 100%
Braking transistor
Separately mounted option
Minimum resistance value (
Ω
)
Braking resistor
Separately mounted option
DC reactor (DCR)
Separately
mounted option
Must be used. Separately mounted component. Depending on the
shipping destination, not provided with the inverter package.
*11
Applicable safety standards
IEC/EN61800-5-1: 2007
Enclosure (IEC60529)
IP00, UL open type
Cooling method
Fan cooling
Weight / Mass (kg) [lbs]
30
[66]
33
[73]
40
[88]
62
[137]
63
[139]
95
[209]
96
[212]
130
[287]
140
[309]
Note: A box (
) in the above table replaces GA, GB or C depending on the model.
*1 Fuji 4-pole standard motor
*2 Rated capacity is calculated assuming the rated output voltage as 440 V (460 V).
*3 Output voltage cannot exceed the power supply voltage.
*4 Setting the carrier frequency (F26) to the following value or above requires current derating.
HHD spec of type FRN0022
E2■
-4
to FRN0168
E2■
-4
: 10 kHz,
HHD spec of type FRN0203
E2■
-4
to FRN0590
E2■
-4
: 6 kHz,
If reduction is necessary, for details, refer to Figure 10.4-1 in Chapter 10 “10.4.2 Guideline for selecting
inverter drive mode and capacity.”
*5
Inverters of FRN0203E2■
-4
or above (400 V class series) are equipped with a power switching connector.
Use the connector depending upon the applied voltage. For details, refer to Chapter 2 “2.2.7 Switching
Connector.”
*6
67
×
(V)
voltage
average
phase
-
Three
(V)
voltage
Min.
-
(V)
voltage
Max.
=
(%)
unbalance
Voltage
(IEC 61800-3)
If the unbalance ratio is 2% to 3%, use an optional AC reactor (ACR).
*7 This specification is an estimated value to be applied when the power supply capacity is 500 kVA (Inverter
capacity × 10 when the capacity exceeds 50 kVA) and the power supply with %X = 5% is connected. When
applying with motors of 75 kW (100 HP) or above, a DC reactor (DCR) should be used.
*8 This specification applies when a DC reactor (DCR) is used.
*9 Average braking torque for the motor running alone. It depends on the efficiency of the motor.
*11 Please consult your Fuji Electric sales representative.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......