Stop bit selection (y07, y17)
Sets the stop bit.
•
For inverter supporting loader (via RS-485):
The value does not need to be set since it automatically
becomes 1 bit.
For Modbus RTU: The value does not need to be set since it
is automatically determined in conjunction with the parity bit
(function y06, y16).
y07 and y17 data
Function
0
2 bits
1
1 bit
■
Communication time-out detection timer (y08, y18)
Sets a period from the time when the system detects
communication time-out (for any reason such as
disconnection in equipment that periodically access to the
station within a specific time) during the operation using the
RS-485 communication, until the time when the system
processes the communication errors.
For details on processing communication errors, refer to y02
and y12.
y08 and y18 data
Function
0
Disconnection is not
detected.
1 to 60
Detection time from 1 to
60 (s)
■
Response interval time (y09, y19)
Sets a period from the time when the system receives a request from host equipment (upper equipment such as
computer or PLC) until the time when it returns a response. In case of the host equipments that are slow to process
the task from completed transmission to completed reception preparation, a timing can be synchronized by setting
a response interval time.
•
Data setting range: 0.00 to 1.00 (s)
T1 = Response interval time + α
α: Processing time inside the inverter. It varies depending on the timing and
command.
For details, refer to the RS-485 Communication User’s Manual.
To set an inverter by the inverter supporting loader via the RS-485 communication, consider the
performance and condition of the computer and converter (such as USB-RS-485 converter).
(Some converters monitor communication status and switch transmission and reception with timer.)
■
Protocol selection (y10, y20)
Selects a communication protocol.
y10 and y20 data
Function
0
Modbus RTU protocol
1
FRENIC Loader protocol
2
Fuji general-purpose inverter protocol
Host device
Request
Inverter
Response
T1
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......