![Fuji Electric FRENIC-Ace series User Manual Download Page 380](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846380.webp)
5.3 Description of Function Codes
5-210
J15
J16
J17
J23
J24
PID control (Sleep frequency)
PID control (Sleep timer)
PID control (Wakeup frequency)
PID control (Wakeup level of PID error)
PID control (Wakeup timer)
Sleep function (J15 to J17, J23, J24)
J15 to J17 configure the sleep function in pump control, a function that stops the inverter when the discharge
pressure increases, causing the volume of water to decrease.
When the discharge pressure has increased, decreasing the reference frequency (output of the PID processor)
below the sleep level (J15) for the period specified sleep timer (J16), the inverter decelerates to stop, while PID
control itself continues to operate. When the discharge pressure decreases, increasing the reference frequency
(output of the PID processor) above the wakeup frequency (J17), the inverter resumes operation.
The restarting conditions can be adjusted with J23 and J24.
■
PID control (Sleep frequency) (J15)
J15 specifies the frequency which triggers slow flowrate stop of inverter.
■
PID control (Sleep timer) (J16)
J16 specifies the period from when the PID output drops below the frequency specified by J15 until the inverter
starts deceleration to stop.
■
PID control (Wakeup frequency) (J17)
J17 specifies the wakeup
frequency. Set J17 to a frequency higher than the sleep frequency (J15). If the specified
wakeup
frequency is lower than the sleep frequency, the sleep frequency is ignored; the sleep function is triggered
when the output of the PID processor drops below the specified wakeup
frequency.
■
Assignment of “PID-STP” (“Under sleep mode of PID control”) (E20, E21 and E27, data = 44)
“PID-STP” (“Under sleep mode of PID control”) is ON when the inverter is in a stopped state due to the sleep
function under PID control. PID-STP should be assigned if it is necessary to output a signal to indicate that the
inverter is stopped.
For the sleep function, see the chart below.
Output frequency
Acceleration time
setting
Starting
frequency
Deceleration time setting
PID output (MV)
Wakeup frequency
Sleep frequency
Sleep timer
MV increased
again by
decrease of
pressure (PV)
Feedback (PV)
Pressure in pipeline
Pressure decrease
started by opening tap
Pressure increased by
inverter restart
Run command
Under sleep mode of PID
control PID-STP
Time
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......