11.2 Currents Flowing Across the Inverter Terminals
11-4
Table 11.2-1 Currents Flowing across the Inverter Terminals (continued)
HND mode (kW rating motor)
Power supply
voltage
Nominal
applied
motor
(kW)
Inverter type
50Hz, 200V/400V
60Hz, 220V/440V
Braking
resistor
circuit
current
(A)
Input RMS current (A)
DC link
bus
current
(A)
Input RMS current (A)
DC link
bus
current
(A)
DC reactors (DCRs)
DC reactors (DCRs)
w/ DCR
w/o DCR
w/ DCR
w/o DCR
Three-phase
200V/220V
0.2
FRN0001E2■
-2
0.93
1.8
1.1
0.85
1.7
1.0
0.82
0.4
FRN0002E2■
-2
1.6
2.6
2.0
1.5
2.6
1.8
1.2
0.75
FRN0004E2■
-2
3.0
4.9
3.7
2.8
4.9
3.4
1.2
1.1
FRN
0006E2■
-2
4.3
6.7
5.3
5.2
6.7
6.4
1.6
2.2
FRN0010E2■
-2
8.3
12.8
10.2
7.6
12.3
9.3
3.6
3.0
FRN0012
E2■
-2
11.7
17.9
14.3
12.7
17.9
15.6
3.5
5.5
FRN002
0E2■
-2
19.9
28.5
24.4
19
28.4
23.3
4.1
7.5
FRN0030E2
■
-2
28.8
42.7
35.3
26.0
38.5
31.9
6.4
11
FRN0040E2
■
-2
42.2
60.7
51.7
38.0
54.7
46.6
6.1
15
FRN0056E2
■
-2
57.6
80.0
70.6
52.0
72.2
63.7
9.1
18.5
FRN0069E2
■
-2
71.0
97.0
87.0
64.0
87.4
78.4
11.0
22
FRN0088E2■
-2
84.4
112
103
76.0
101
93.1
14
30
F
RN0115E2■
-2
114
151
140
103
136
126
15
Three-phase
400V/440V
0.75
FRN0002E2■
-4
1.5
2.7
1.8
1.4
2.7
1.7
0.80
1.1
FRN
0004E2■
-4
2.1
3.9
2.6
1.9
3.9
2.3
1.1
2.2
FRN0006E2■
-4
4.2
7.3
5.1
3.8
7.1
4.7
1.8
3.0
FRN0007
E2■
-4
5.8
11.3
7.1
5.3
10.2
6.5
1.8
5.5
FRN0012
E2■
-4
10.1
16.8
12.4
9.1
15.7
11.1
2.1
7.5
FRN0022E2
■
-4
14.4
23.2
17.7
13.0
21.0
16.0
3.2
11
FRN0029E2
■
-4
21.1
33.0
25.9
19.0
29.8
23.3
3.1
15
FRN0037E2
■
-4
28.8
43.8
35.3
26.0
39.5
31.9
4.5
18.5
FRN0044E2
■
-4
35.5
52.3
43.5
32.0
47.1
39.2
5.7
22
FRN0059E2
■
-4
42.2
60.6
51.7
38.0
54.6
46.6
7.2
30
FRN0072E2
■
-4
57.0
77.9
69.9
51.4
70.2
63.0
7.7
37
FRN0085E2
■
-4
68.5
94.3
83.9
61.8
85.0
75.7
10
45
FRN0105E2
■
-4
83.2
114
102
75.0
103
91.9
12
55
FRN0139E2
■
-4
102
140
125
91.9
126
113
15
75
FRN0168E2
■
-4
138
-
169
124
-
152
19
90
FRN0203E2
■
-4
164
-
201
148
-
181
24
110
FRN0240E2
■
-4
201
-
246
181
-
222
31
132
FRN0290E2
■
-4
238
-
292
214
-
263
35
160
FRN0361E2
■
-4
286
-
350
258
-
315
42
200
FRN0415E2
■
-4
357
-
437
321
-
394
50
220
FRN0520E2
■
-4
390
-
478
351
-
430
62
280
FRN0590E2
■
-4
500
-
613
450
-
552
71
Note:
A box (■) in the above table replaces S (Basic type) or E (EMC filter built
-in type) depending on the enclosure.
A box (
) in the above table replaces GA, GB or C depending on the model.
•
Inverter efficiency is calculated using values suitable for each inverter model. The input route mean square
current is calculated based on a power supply capacity of 500 kVA (or 10 times as large as the inverter’s
capacity when the inverter’s capacity exceeds 50 kVA), and a power supply reactance of 5%.
•
The input RMS current listed in the above table will vary in inverse proportion to the power supply voltage, such
as 480 VAC.
•
The braking current is always constant, independent of braking resistor specifications, including standard and
10%ED models.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......