![Fuji Electric FRENIC-Ace series User Manual Download Page 659](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846659.webp)
11.12 Surge Suppression Unit (SSU)
11-55
SE
LEC
TI
N
G
P
E
R
IPH
ER
AL
E
Q
U
IPM
E
N
T
Chap 1
1
11.12 Surge Suppression Unit (SSU)
■
Dimensions
• 50 m spec: SSU 50TA
-NS
• 100 m spec: SSU 100TA
-NS
■
Effects of surge suppression units (voltage waveform between motors)
■
Basic specifications
Item
Specifications
Type
SSU 50TA-NS
SSU 100TA-NS
Applicable wiring length
Up to 50 m (164 ft)
Up to 100 m (328 ft)
Power supply voltage
200 V and 400 V classes; PWM converter is applicable.
Inverter capacity
Up to 75 kW (90 kW or larger requires customized service.)
Output frequency
Up to 400 Hz
Carrier frequency
Up to 15 kHz (Cannot be used at 16 kHz.)
Enclosure
IP20
Installation environment
Ambient temperature: -20 to +40°C, relative humidity: 85% RH or below,
vibration: 0.7 G or less, Installation: horizontally
Dielectric strength voltage
2500 VAC, 1 min
If the drive wire for the motor is long, an extremely low surge voltage (micro surge) occurs at the
wire end connected to the motor. Surge voltage causes motor degradation, insulation
breakdown, or increased noises. The surge suppression unit (SSU) suppresses the surge
voltage. It features the connectivity for all inverter capacities and easy wiring work.
Surge suppression mechanism
Pulse
Surge suppression unit
Surge absorption
Power
supply
•
Motor/inverter capacity: 3.7 kW
•
Running status: No-load
•
Wiring length: 50 m
•
Power supply voltage:
Three-phase 400 V
•
Motor/inverter capacity: 75 kW
•
Running status: No-load
•
Wiring length: 100 m
•
Power supply voltage:
Three-phase 400 V
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......