9.2 CANopen Communication
9-27
CO
M
M
U
NI
C
AT
IO
N
FUN
CT
IO
N
S
Chap 9
Index
(Hex) Sub
Name
Description
Data type
Data hold Access
1600
- 1st Receive PDO Mapping Parameter
RECORD
-
-
0 Number of mapped
objects
Number of mapped objects (up to 4)
Default value: 1
UNSIGNED8
-
RW
1 PDO mapping entry1
Default value: 0x60400010 (Controlword)
UNSIGNED32
-
RW
2 PDO mapping entry2
Default value: No mapping
UNSIGNED32
-
RW
3 PDO mapping entry3
Default value: No mapping
UNSIGNED32
-
RW
4 PDO mapping entry4
Default value: No mapping
UNSIGNED32
-
RW
1601
- 2nd Receive PDO Mapping Parameter
RECORD
-
-
0 Number of mapped
objects
Number of mapped objects (up to 4)
Default value: 2
UNSIGNED8
-
RW
1 PDO mapping entry1
Default value: 0x60400010 (Controlword)
UNSIGNED32
-
RW
2 PDO mapping entry2
Default value: 0x60420010 (vl target
velocity)
UNSIGNED32
-
RW
3 PDO mapping entry3
Default value: No mapping
UNSIGNED32
-
RW
4 PDO mapping entry4
Default value: No mapping
UNSIGNED32
-
RW
1602
- 3rd Receive PDO Mapping Parameter
RECORD
-
-
0 Number of mapped
objects
Number of mapped objects: 4
UNSIGNED8
-
R
1 PDO mapping entry1
Fixed value: 0x5F020110
(writing function code mapping 1)
UNSIGNED32
-
R
2 PDO mapping entry2
Fixed value: 0x5F020210
(writing function code mapping 2)
UNSIGNED32
-
R
3 PDO mapping entry3
Fixed value: 0x5F020310
(writing function code mapping 3)
UNSIGNED32
-
R
4 PDO mapping entry4
Fixed value: 0x5F020410
(writing function code mapping 4)
UNSIGNED32
-
R
1800
- 1st Transmit PDO Communication Parameter
RECORD
-
-
0 Largest sub-index
Maximum sub-index No.: 5
UNSIGNED8
-
R
1 COB-ID
COB-ID of TPDO No.1
Default value: 0x180 + node ID
UNSIGNED32
Y
RW
*1
2 Transmission type
Select the transmission type
Default value: 255
(Change of state event)
(refer to Table 9.2-11, Table 9.2-12)
UNSIGNED8
Y
RW
3 Inhibit time
Waiting time for transmission (unit: 0.1 ms)
Default value: 100 (10.0 ms)
UNSIGNED16
Y
RW
*2
5 Event timer
Periodical transmission interval (unit: 1 ms)
Transmission type
Valid at the time of 254 or 255.
Default value: 0 (not used)
UNSIGNED16
Y
RW
1801
- 2nd Transmit PDO Communication Parameter
RECORD
-
-
0 Largest sub-index
Maximum sub-index No.: 5
UNSIGNED8
-
R
1 COB-ID
COB-ID of TPDO No.2
Default value: 0x280 + node ID
UNSIGNED32
Y
RW
*1
2 Transmission type
Select the transmission type
Default value: 255
(Change of state event)
(refer to Table 9.2-11, Table 9.2-12)
UNSIGNED8
Y
RW
3 Inhibit time
Waiting time for transmission (unit: 0.1 ms)
Default value: 100 (10.0 ms)
UNSIGNED16
Y
RW
*2
5 Event timer
Periodical transmission interval (unit: 1 ms)
Transmission type
Valid at the time of 254 or 255.
Default value: 0 (not used)
UNSIGNED16
Y
RW
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......