9.2 CANopen Communication
9-26
Index
(Hex) Sub
Name
Description
Data type
Data hold Access
100A
- Manufacturer SW
version
Software version:
“E2S1-” + code M25
(same as the inverter ROM Version)
STRING
-
R
100C
- Guard time
Guarding receive cycle setting (ms)
Default value: 0 (no operation)
UNSIGNED16
Y
RW
100D
- Life time factor
Guarding time coefficient
Default value: 0 (no operation)
UNSIGNED8
Y
RW
1014
- COB-ID EMCY
COB-ID of the EMCY message
Read value: node ID
UNSIGNED32
-
R
1016
- Consumer heartbeat time
ARRAY
-
-
0 Number of entries
Number of configurations
UNSIGNED8
-
R
1 Consumer heartbeat
time
Upper word: Node ID to be monitored
Lower word: Heartbeat monitoring cycle
Default value: 0 (no operation)
UNSIGNED32
Y
RW
1017
- Producer heartbeat time
Transmission cycle of Heartbeat message
Default value: 0 (no operation)
UNSIGNED16
Y
RW
1018
- Identity Object
RECORD
-
-
0 Number of entries
Number of subindexes: 1
UNSIGNED8
-
R
1 Vendor ID
0x0000025E
(Fuji Electric Group)
UNSIGNED32
-
R
1029
- Error behavior
ARRAY
-
-
0 Number of entries
Highest sub-index supported
UNSIGNED8
-
R
1 Communication error
Default value: 0 (change to pre-operational)
(For details, refer to the Table 9.2-21)
UNSIGNED8
-
RW
1200
- Server SDO parameter
RECORD
-
-
1 COB-ID C->S (rx)
0x600 + node ID.
UNSIGNED32
-
R
2 COB-ID S->C (tx)
0x580 + node ID.
UNSIGNED32
-
R
1400
- 1st Receive PDO Communication Parameter
RECORD
-
-
0 Number of entries
Number of subindexes: 2
UNSIGNED8
-
R
1 COB-ID
COB-ID of RPDO No.1
Default value: 0x200 + node ID
UNSIGNED32
Y
RW
*1
2 Transmission type
Select the transmission type
Default value: 255
(Change of state event)
(refer to Table 9.2-9, Table 9.2-10)
UNSIGNED8
Y
RW
1401
- 2nd Receive PDO Communication Parameter
RECORD
-
-
0 Number of entries
Number of subindexes: 2
UNSIGNED8
-
R
1 COB-ID
COB-ID of RPDO No.2
Default value: 0x300 + node ID
UNSIGNED32
Y
RW
*1
2 Transmission type
Select the transmission type
Default value: 255
(Change of state event)
(refer to Table 9.2-9, Table 9.2-10)
UNSIGNED8
Y
RW
1402
- 3rd Receive PDO Communication Parameter
RECORD
-
-
0 Number of entries
Number of subindexes: 2
UNSIGNED8
-
R
1 COB-ID
COB-ID of RPDO No.3
Default value: 0x400 + node ID
UNSIGNED32
Y
RW
*1
2 Transmission type
Select the transmission type
Default value: 255
(Change of state event)
(refer to Table 9.2-9, Table 9.2-10)
UNSIGNED8
Y
RW
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......