9.2 CANopen Communication
9-23
CO
M
M
U
NI
C
AT
IO
N
FUN
CT
IO
N
S
Chap 9
9.2.6 SDO protocol
[ 1 ] About SDO
The SDO (Service Data Object) protocol is used to set and adjust the inverter. SDO enables to access all objects
(parameters) of the inverter. The CANopen communication of inverter supports a single Server SDO.
For information about how to transmit data in SDO, refer to the manual of the master or configuration tool.
For information about the objects, refer to “9.2.8 Object list”.
[ 2 ] Response on SDO error
If the access in SDO has an error, this communication card returns an Abort code listed in Table 9.2-13.
Table 9.2-13 Abort Codes on SDO Access Error
Abort codes
Description
0503 0000
Error on divided SDO transmission: Improper toggle bit
0504 0000
Response timeout error
0601 0000
Unsupported access to an object
0601 0001
Write only object is read
0601 0002
Read only object is written
0602 0000
Parameter does not exist
0604 0041
Object cannot be mapped to the PDO.
0604 0042
The number and length of the objects to be mapped would exceed PDO length.
0606 0000
Writing while EEPROM is running of inverter
0607 0010
Different parameter’s data type
0607 0012
Data type does not match, length of service parameter too high.
0607 0013
Data type does not match, length of service parameter too low.
0609 0011
Accessed to the object without subindex
0609 0030
The value written is out of range
0609 0031
Value of parameter written too high.
0609 0032
Value of parameter written too low.
0800 0021
Inverter function code write error
(SO1, SO5, and SO6 are written by CANopen when the link to RS-485 communication port is valid)
0800 0022
Write to inverter function code is disabled (running, writing, digital input terminal is ON)
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......