5.3 Description of Function Codes
5-112
UPS operation (When
BATRY/UPS
= ON)
(1) The inverter can run the motor starting from the voltage level specified with H111.
(2) The
RDY
(“Inverter ready to run” signal) is forced to go OFF.
(3) The circuit of charging resistor is shorted (73X = ON) after the delay time T1 (0.2 sec) from the timing which
BATRY/UPS
terminal being turned on and the DC link bus voltage exceeds UPS operation level (specified
with H111) or above. In addition, after the delay time T2 (max. 0.1 sec.), the UPS operation starts. For T1
specifications, see the table below.
(4) During the UPS operation, the inverter can run the motor.
(5) S-curve acceleration/deceleration becomes invalid.
Power supply condition
FRN0115E2
-2
or below
FRN0085E2
-4
or below
FRN0012E2
-7
or below
Time required for turning on the control power supply, switching to the
power supply from the battery, and then to turning on the charging resistor
short circuit 73X
T1=0.2 sec
Time required from the occurrence of momentary power failure in the
control power supply ON status, switching to the power supply from the
battery, and turning on of the short circuit 73X for the charging resistor
Figure 5.3-6 UPS operation timing chart
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......