Terminal [C1] (C1 function) range / polarity selection (C40)
C40 data
Terminal input range
Handling when bias value is set to minus
0
4 to 20 mA (Factory default)
Limit below 0 point with 0
1
0 to 20mA
10
4 to 20mA
Enable below 0 point as minus value.
11
0 to 20mA
■
Terminal [C1] (V2 function) polarity selection (C45)
C45 data
Modes for terminal inputs
0
0 to +10V
When bias value is set to minus, enable below 0 point as a minus value.
1
0 to +10V (factory default)
When bias value is set to minus, limit below 0 point by 0.
In order to use [C1] terminal as C1 function, V2 function, and PTC function, the following setting are necessary.
[C1] terminal
SW3
SW4
E59
H26
C40
When using C1 function (4 to 20 mA)
C1 side
AI side
0
0
0,10
When using C1 function (0 to 20 mA)
C1 side
AI side
0
0
1,11
When using V2 function (0 to +10V)
V2 side
AI side
1
0
Not relevant
When using PTC function
C1 side
PTC side
Not relevant
1, 2
Not relevant
For details of SW3 and SW4, refer to Chapter 2, Section 2.2.8.
Caution is necessary because if the above switch settings are not performed accurately, unexpected frequency
setting may be performed for the inverter.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......