12.1 Standard Model
12-17
SP
EC
IF
IC
AT
IO
N
S
Chap 1
2
■
Standard-model, Single-phase 200 V (230 V) class series (HHD-mode: 0.1 kW to 2.2 kW)
Item
Specifications
Type (FRN_ _ _ _E2S-7
)
0001
0002
0003
0005
0008
0011
Nominal applied motor (kW) [HP]
(Output rating)
*1
0.1
[1/8]
0.2
[1/4]
0.4
[1/2]
0.75
[1]
1.5
[2]
2.2
[3]
O
utput r
ati
ngs
Rated capacity (kVA)
*2
0.3
[0.3]
0.6
[0.6]
1.1
[1.2]
1.9
[2.0]
3.0
[3.2]
4.2
[4.4]
Rated voltage (V)
*
3
Three-phase 200 to 240 V (with AVR function)
Rated current (A)
*
4
0.8
1.6
3.0
5.0
8.0
11
Overload capability
150%-1 min, 200%-0.5 s
Input powe
r
Voltage, frequency
Single-phase 200 to 240 V, 50/ 60 Hz
Allowable voltage/frequency
Voltage: +10 to -10%, Frequency: +5 to -5%
Rated input current
*7
(w/o DCR) (A)
1.8
3.3
5.4
9.7
16.4
24.8
(with DCR) (A)
1.1
2.0
3.5
6.4
11.6
17.5
Required capacity
(with DCR) (kVA)
*8
0.3
0.4
0.7
1.3
2.4
3.5
B
rak
ing
Torque (%)
*9
150%
100%
70%
40%
DC braking
Braking starting frequency: 0.0 to 60.0 Hz, Braking time: 0.0 to 30.0 s,
Braking level: 0 to 100%
Braking transistor
Built-in as standard
Minimum resistance value (
Ω
)
100
40
Braking resistor
Separately mounted option
DC reactor (DCR)
Separately mounted option
Applicable safety standards
IEC/EN61800-5-1: 2007
Enclosure (IEC60529)
IP00, UL open type
Cooling method
Natural cooling
Fan cooling
Weight / Mass (kg) [lbs]
0.5
[1.1]
0.5
[1.1]
0.6
[1.3]
0.9
[2.0]
1.6
[3.5]
1.8
[4.0]
Note: A box (
) in the above table replaces GA, GB or C depending on the model.
*1 Fuji 4-pole standard motor
*2 Rated capacity is calculated assuming the rated output voltage as 220 V (230 V).
*3 Output voltage cannot exceed the power supply voltage.
*4 Setting the carrier frequency (F26) to the following value or above requires current derating.
HHD spec of type FRN0001
E2■
-4
to FRN0011
E2■
-4
: 8 kHz,
If reduction is necessary, for details, refer to Figure 10.4-1 in Chapter 10
“10.4.2 “Guideline for selecting
inverter drive mode and capacity.”
*7 This specification is an estimated value to be applied when the power supply capacity is 500 kVA (Inverter
capacity × 10 when the capacity exceeds 50 kVA) and the power supply with %X = 5% is connected.
*8 This specification applies when a DC reactor (DCR) is used.
*9 Average braking torque for the motor running alone. It depends on the efficiency of the motor.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......