5.3 Description of Function Codes
5-140
C05 to C19 Multistep frequency 1 to 15
■
These function codes specify 15 frequencies required for driving the motor at frequencies 1 to 15.
Turning terminal commands “SS1”, “SS2”, “SS4” and “SS8” ON/OFF selectively switches the reference frequency
of the inverter in 15 steps. To use this features, you need to assign “SS1”, “SS2”, “SS4” and “SS8” (“Select
multistep frequency”) to the digital input terminals with E01 to E05 (data = 0, 1, 2, and 3).
■
Multistep frequency 1 to 15 (C05 through C19)
•
Data setting range: 0.00 to 500.0 (Hz)
The combination of “SS1”, “SS2”, “SS4” and “SS8” and the selected frequencies is as follows.
“SS8”
“SS4”
“SS2”
“SS1”
Selected frequency command
OFF
OFF
OFF
OFF
Other than multistep frequency*
OFF
OFF
OFF
ON
C05 (Multistep frequency 1)
OFF
OFF
ON
OFF
C06 (Multistep frequency 2)
OFF
OFF
ON
ON
C07 (Multistep frequency 3)
OFF
ON
OFF
OFF
C08 (Multistep frequency 4)
OFF
ON
OFF
ON
C09 (Multistep frequency 5)
OFF
ON
ON
OFF
C10 (Multistep frequency 6)
OFF
ON
ON
ON
C11 (Multistep frequency 7)
ON
OFF
OFF
OFF
C12 (Multistep frequency 8)
ON
OFF
OFF
ON
C13 (Multistep frequency 9)
ON
OFF
ON
OFF
C14 (Multistep frequency 10)
ON
OFF
ON
ON
C15 (Multistep frequency 11)
ON
ON
OFF
OFF
C16 (Multistep frequency 12)
ON
ON
OFF
ON
C17 (Multistep frequency 13)
ON
ON
ON
OFF
C18 (Multistep frequency 14)
ON
ON
ON
ON
C19 (Multistep frequency 15)
* “Other than multistep frequency” includes frequency setting 1 (F01), frequency setting 2 (C30) and other
frequency command sources except multistep frequency commands.
C20
Jogging frequency
Related function codes: H54 and H55 Acceleration/Deceleration time (Jogging)
H54 and H55 Acceleration/Deceleration time (jogging)
C20 specifies the operating condition (frequency) to apply in jogging operation.
Function code
Data setting range
Description
C20
Jogging frequency
0.00 to 500.00 (Hz)
Reference frequency for jogging
operation
H54
Acceleration time (Jogging)
0.00 to 6000 s
Acceleration time for jogging
operation
H55
Deceleration time (Jogging)
0.00 to 6000 s
Deceleration time for jogging
operation
For details about jogging operation, refer to Chapter 3 “3.3.6 Jogging operation.”
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......