12.1 Standard Model
12-1
SP
EC
IF
IC
AT
IO
N
S
Chap 1
2
12.1 Standard Model
12.1.1 ND-mode inverters for general load
■
Standard-model, Three-phase 400 V (460 V) class series (ND-mode: 0.75 kW to 5.5 kW)
Item
Specifications
Type (FRN_ _ _ _E2S-4
)
0002
0004
0006
0007
0012
Nominal applied motor (kW) [HP]
(Output rating)
*1
0.75
[1]
1.5
[2]
2.2
[3]
3.0
[4]
5.5
[7.5]
O
utput r
ati
ngs
Rated capacity (kVA)
*2
1.6
[1.7]
3.1
[3.3]
4.2
[4.4]
5.3
[5.5]
9.1
[9.6]
Rated voltage (V)
*3
Three-phase 380 to 480 V (with AVR function)
Rated current (A)
*4
2.1
4.1
5.5
6.9
12
Overload capability
120%-1 min
Input powe
r
Voltage, frequency
Three-phase 380 to 480 V, 50/60 Hz
Allowable voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*6
, Frequency: +5 to -5%
Rated input current
*7
(w/o DCR) (A)
2.7
4.8
7.3
11.3
16.8
(with DCR) (A)
1.5
2.9
4.2
5.8
10.1
Required capacity
(with DCR) (kVA)
*8
1.1
2.1
3.0
4.1
7.0
B
rak
ing
Torque (%)
*9
53%
50%
48%
29%
27%
DC braking
Braking starting frequency: 0.0 to 60.0 Hz, Braking time: 0.0 to 30.0 s,
Braking level: 0 to 60%
Braking transistor
Built-in as standard
Minimum resistance value (
Ω
)
200
160
130
Braking resistor
Separately mounted option
DC reactor (DCR)
Separately mounted option
Applicable safety standards
IEC/EN61800-5-1: 2007
Enclosure (IEC60529)
IP20, UL open type
Cooling method
Natural cooling
Fan cooling
Weight / Mass (kg) [lbs]
1.2
[2.6]
1.5
[3.3]
1.5
[3.3]
1.6
[3.5]
1.9
[4.2]
Note: A box (
) in the above table replaces GA, GB or C depending on the model.
*1 Fuji 4-pole standard motor
*2 Rated capacity is calculated assuming the rated output voltage as 440 V (460 V).
*3 Output voltage cannot exceed the power supply voltage.
*4 Setting the carrier frequency (F26) to the following value or above requires current derating.
ND spec. of all types : 4 kHz
If the ambient temperature is 40°C (104°F) or above, derating of 2%/°C (2%/1.8°F) relative to the rated
current given in this manual is required. For details, refer to Chapter 10 “10.4.2 Guideline for selecting
inverter drive mode and capacity.”
*6
67
×
(V)
voltage
average
phase
-
Three
(V)
voltage
Min.
-
(V)
voltage
Max.
=
(%)
unbalance
Voltage
(IEC 61800-3)
If the unbalance ratio is 2% to 3%, use an optional AC reactor (ACR).
*7 This specification is an estimated value to be applied when the power supply capacity is 500 kVA (Inverter
capacity × 10 when the capacity exceeds 50 kVA) and the power supply with %X = 5% is connected.
*8 This specification applies when a DC reactor (DCR) is used.
*9 Average braking torque for the motor running alone. It depends on the efficiency of the motor.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......