Power supply
voltage
Nominal applied motor
(kW)
Inverter type
HHD/HND/HD/
ND mode
Fuse rating
(A)
Three phase 400V
0.4
FRN0002E2
■
-4
HHD
3(IEC60269-2)
0.75
HND/HD
6(IEC60269-2)
0.75
ND
6(IEC60269-2)
0.75
FRN0004E2
■
-4
HHD
6(IEC60269-2)
1.1
HND/HD
10(IEC60269-2)
1.5
ND
10(IEC60269-2)
1.5
FRN0006E2
■
-4
HHD
10(IEC60269-2)
2.2
HND/HD
15(IEC60269-2)
2.2
ND
15(IEC60269-2)
2.2
FRN0007E2
■
-4
HHD
15(IEC60269-2)
3.0
HD
20(IEC60269-2)
3.0
ND
20(IEC60269-2)
3.7
FRN0012E2
■
-4
HHD
20(IEC60269-2)
5.5
HD
30(IEC60269-2)
5.5
ND
30(IEC60269-2)
5.5
FRN0022E2
■
-4
HHD
80(IEC60269-4)
7.5
HND/HD
80(IEC60269-4)
11
ND
80(IEC60269-4)
7.5
FRN0029E2
■
-4
HHD
80(IEC60269-4)
11
HND/HD
80(IEC60269-4)
15
ND
125(IEC60269-4)
11
FRN0037E2
■
-4
HHD
125(IEC60269-4)
15
HND/HD
125(IEC60269-4)
18.5
ND
125(IEC60269-4)
15
FRN0044E2
■
-4
HHD
160(IEC60269-4)
18.5
HND/HD
160(IEC60269-4)
22
ND
160(IEC60269-4)
18.5
FRN0059E2
■
-4
HHD
160(IEC60269-4)
22
HND/HD
160(IEC60269-4)
30
ND
160(IEC60269-4)
22
FRN0072E2
■
-4
HHD
160(IEC60269-4)
30
HND/HD
160(IEC60269-4)
37
ND
160(IEC60269-4)
30
FRN0085E2
■
-4
HHD
250(IEC60269-4)
37
HND/HD
250(IEC60269-4)
45
ND
250(IEC60269-4)
37
FRN0105E2
■
-4
HHD
315(IEC60269-4)
45
HND/HD
315(IEC60269-4)
55
ND
315(IEC60269-4)
45
FRN0139E2
■
-4
HHD
315(IEC60269-4)
55
HND/HD
315(IEC60269-4)
75
ND
315(IEC60269-4)
55
FRN0168E2
■
-4
HHD
350(IEC60269-4)
75
HND/HD
350(IEC60269-4)
90
ND
350(IEC60269-4)
75
FRN0203E2
■
-4
HHD
350(IEC60269-4)
90
HND/HD
350(IEC60269-4)
110
ND
350(IEC60269-4)
90
FRN0240E2
■
-4
HHD
350(IEC60269-4)
110
HND/HD
350(IEC60269-4)
132
ND
450(IEC60269-4)
110
FRN0290E2
■
-4
HHD
400(IEC60269-4)
132
HND/HD
400(IEC60269-4)
160
ND
500(IEC60269-4)
132
FRN0361E2
■
-4
HHD
450(IEC60269-4)
160
HND/HD
450(IEC60269-4)
200
ND
550(IEC60269-4)
160
FRN0415E2
■
-4
HHD
500(IEC60269-4)
200
HND/HD
500(IEC60269-4)
220
ND
630(IEC60269-4)
200
FRN0520E2
■
-4
HHD
550(IEC60269-4)
220
HND/HD
550(IEC60269-4)
280
ND
900(IEC60269-4)
220
FRN0590E2
■
-4
HHD
630(IEC60269-4)
280
HND
630(IEC60269-4)
250
HD
630(IEC60269-4)
315
ND
900(IEC60269-4)
Note: A box (
■
) in the above table replaces S (Basic type) or E (EMC filter built-in type) depending on the
enclosure.
A box (
) in the above table replaces GA, GB or C depending on the model.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......