![Fuji Electric FRENIC-Ace series User Manual Download Page 74](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846074.webp)
2.2 Wiring
2-42
2.2.6 Control circuit terminals (common to all models)
[ 1 ] Screw specifications and recommended wire size (control circuit terminals)
The screw specifications and wire sizes to be used for control circuit wiring are shown below.
The control circuit terminal board differs depending on the destination.
Table 2.2-28 Screw Specifications and Recommended Wire Sizes
Terminal symbol
Screw specification
Allowable wire
sizes
Driver
(shape of tip)
Removal size of
wire cover
Gauge size to
insert wire
Size Tightening torque
30A, 30B, 30C
EN1, EN2
M3
0.5 N·m
(4.43 lb-in)
0.14 to 1.5 mm
2
(AWG26 to 16)
Minus
(0.6mm×3.5mm)
6 mm
(0.24 in)
A1
*1
Others
M2
0.19 N·m
(1.68 lb-in)
0.25 to 1 mm
2
(AWG24 to 18)
Minus
(0.4mm×2.5mm)
5 mm
(0.20 in)
φ1.6
* Recommended rod terminal: Phoenix Contact
Refer to Table 2.2-29 for details.
*1 Defined according to IEC/EN 60947-1.
Table 2.2-29 Recommended Rod Terminals
Screw size
Wire size
Type
With insulating collar
Without insulating collar
M3
M2
0.25 mm
2
(AWG24)
AI 0.25-6 BU
A 0.25-7
0.34 mm
2
(AWG22)
AI 0.34-6 TQ
A 0.34-7
0. 5 mm
2
(AWG20)
AI 0.5-6 WH
A 0.5-6
0.75 mm
2
(AWG18)
AI 0.75-6 GY
A 0.75-6
1 mm
2
(AWG18)
AI 1-6 RD
A 1-6
1.5 mm
2
(AWG16)
AI 1.5-6 BK
A 1.5-7
Note) When sizes exceeding the recommended wire sizes are used, the front cover may be pushed outward
depending on the number of wires, causing erroneous operation of the keypad.
[ 2 ] Terminal layout diagram (control circuit terminal)
Model: -GA
Model: -GB/-C
The following terminals may have high voltage when the power is ON.
Control terminals: AUX-contact (30A, 30B, 30C)
Insulation level
Contact output – control circuit : Enhanced insulation (overvoltage category II, degree of contamination 2)
Risk of electric shock exists
Contact output
Enhanced insulation
(Max. 250 VAC overvoltage category II, degree of contamination 2)
Contact output
Enhanced insulation
(Max. 250 VAC overvoltage category II, degree of contamination 2)
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......