5.3 Description of Function Codes
5-275
FU
NCT
IO
N
C
O
DE
S
Chap 5
Setting example 2: Bring multiple output signals in a single signal
If the general-purpose RUN signal is kept ON at restart after momentary power failure, replace an external circuit
that is conventionally needed with a customizable logic sequence to reduce the general-purpose output terminals
and external relays.
To configure this customizable logic, set the function codes as follows. (Timer selection) and (Timer setting) do not
need to be modified if no change is made.
Function code
Setting
value
Settings
Remarks
E20
Terminal [Y1] function
111
Customizable logic output
signal 1 “CL01”
U00
Customizable Logic (Mode selection)
1
Enable
U01
Customizable logic:
Step 1
(Block
selection)
30
Logical OR +
General-purpose timer
Mode selection
U02
(Input 1)
0
During operation “RUN”
U03
(Input 2)
6
Auto-restarting after
momentary power failure “IPF”
U71
Customizable logic
output signal 1
(Output
selection)
1
Output of step 1, “SO01”
U81
(Function
selection)
100
No function assigned “NONE”
Inverter
Customizable logic
Step 1
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......