12.1 Standard Model
12-7
SP
EC
IF
IC
AT
IO
N
S
Chap 1
2
12.1.3 HND-mode inverters for general load
■
Standard-model, Three-phase 200 V (230 V) class series (HND-mode: 0.2 kW to 5.5 kW)
Item
Specifications
Type (FRN_ _ _ _E2S-2
)
0001
0002
0004
0006
0010
0012
*10
0020
*10
Nominal applied motor (kW) [HP]
(Output rating)
*1
0.2
[1/4]
0.4
[1/2]
0.75
[1]
1.1
[1.5]
2.2
[3]
3.0
[4]
5.5
[7.5]
O
utput r
ati
ngs
Rated capacity (kVA)
*2
0.5
[0.5]
0.8
[0.8]
1.3
[1.4]
2.3
[2.4]
3.7
[3.8]
4.6
[4.8]
7.5
[7.8]
Rated voltage (V)
*3
Three-phase 200 to 240 V (with AVR function)
Rated current (A)
*4
1.3
2.0
3.5
6.0
9.6
12
19.6
Overload capability
120%-1 min
Input powe
r
Voltage, frequency
Three-phase 200 to 240 V, 50/60 Hz
Allowable voltage/frequency Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*6
,
Frequency: +5 to -5%
Rated input current
*7
(w/o DCR) (A)
1.8
2.6
4.9
6.7
12.8
17.9
31.9
(with DCR) (A)
0.93
1.6
3.0
4.3
8.3
11.7
19.9
Required capacity
(with DCR) (kVA)
*8
0.4
0.6
1.1
1.5
2.9
4.1
6.9
B
rak
ing
Torque (%)
*9
75%
53%
68%
48%
29%
27%
DC braking
Braking starting frequency: 0.0 to 60.0 Hz, Braking time: 0.0 to 30.0 s,
Braking level: 0 to 80% ( Type FRN0012E2S-2
and FRN0020E2S-2
: 0 to 60% )
Braking transistor
Built-in as standard
Minimum resistance value (
Ω
)
100
40
33
Braking resistor
Separately mounted option
DC reactor (DCR)
Separately mounted option
Applicable safety standards
IEC/EN61800-5-1: 2007
Enclosure (IEC60529)
IP20, UL open type
Cooling method
Natural cooling
Fan cooling
Weight / Mass (kg) [lbs]
0.5
[1.1]
0.5
[1.1]
0.6
[1.3]
0.8
[1.8]
1.5
[3.3]
1.5
[3.3]
1.8
[4.0]
Note: A box (
) in the above table replaces GA, GB or C depending on the model.
*1 Fuji 4-pole standard motor
*2 Rated capacity is calculated assuming the rated output voltage as 220 V (230 V).
*3 Output voltage cannot exceed the power supply voltage.
*4 Setting the carrier frequency (F26) to the following value or above requires current derating.
HND/ND spec. of types FRN0001
E2■
-2
to FRN0020
E2■
-2
: 4 kHz,
If reduction is necessary, for details, refer to Chapter 10, Section 10.4.2 "Guideline for selecting inverter drive
mode and capacity."
*6
67
×
(V)
voltage
average
phase
-
Three
(V)
voltage
Min.
-
(V)
voltage
Max.
=
(%)
unbalance
Voltage
(IEC 61800-3)
If the unbalance ratio is 2% to 3%, use an optional AC reactor (ACR).
*7 This specification is an estimated value to be applied when the power supply capacity is 500 kVA (Inverter
capacity × 10 when the capacity exceeds 50 kVA) and the power supply with %X = 5% is connected.
*8 This specification applies when a DC reactor (DCR) is used.
*9 Average braking torque for the motor running alone. It depends on the efficiency of the motor.
*10 Types FRN0012
E2■
-2
and FRN0020
E2■
-2
are ND spec; allowable ambient temperature 40°C (+104°F)
or less. The rated output current is decreased 1% for every 1°C (1.8°F) when ambient temperature is +40°C
(+104°F) or more.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......