9.2 CANopen Communication
9-25
CO
M
M
U
NI
C
AT
IO
N
FUN
CT
IO
N
S
Chap 9
9.2.8 Object list
This chapter describes the objects (parameters) supported by the CANopen communication of inverter. The
objects are classified into three types of areas.
(1) Communication profile area (Indexes: 1000 to 1A02)
The objects common to all devices for the CANopen communication. This area is defined in the CANopen
specifications DS 301.
(2) Manufacturer specific profile area (Indexes: 2200 to 5F2A)
The objects only for our company. It is possible to access the inverter function codes, for example. Since they are
dedicated objects, they are not compatible with CANopen devices provided by other manufacturer.
(3) Standard device profile area (Indexes: 6000 to 6078)
The objects for controlling the inverter. This area is standardized in the CANopen specifications DSP 402 and is
compatible with the devices provided by other companies.
[ 1 ] Objects in the communication profile area
Table 9.2-15 lists the objects in the communication profile area. In the access field, R represents read only, RW
represents readable & writable. In the data hold field, “Y” represents that the written data is held after the power
OFF.
Table 9.2-15 Objects in the Communication Profile Area
Index
(Hex) Sub
Name
Description
Data type
Data hold Access
1000
- Device type
Fixed at 0x10192
UNSIGNED32
-
R
1001
- Error register
1: Error, 0: No error
UNSIGNED8
-
R
1003
- Pre-defined error field
ARRAY
-
-
0 Number of errors
Number of errors occurred
1: one error, 0: no error
UNSIGNED8
-
R
1 Standard error field
Displays the code of the occurring error
(For details, refer to the Table 9.2-22)
UNSIGNED32
-
R
1005
- COB-ID SYNC
COB-ID of the SYNC message
Default value: 0x080
UNSIGNED32
Y
RW
1008
- Manufacturer device
name
Device name:
Built-in CAN: “FRN-E2-COP”
Option CAN: “OPC-E2-COP”
(ASCII) fixed
STRING
-
R
1009
- Manufacturer HW
version
Hardware version:
“SP0146” (ASCII)
Control PCB No. for E2S
STRING
-
R
1010
- Store parameter settings
ARRAY
-
0 Number of entries
Number of subindexes
UNSIGNED8
-
R
1 Store all parameters
Save All Parameter
UNSIGNED32
-
RW
2 Store communication
parameters
Save communication parameters
(Object 1000h to 1A02h )
UNSIGNED32
-
RW
3 Store application
parameters
Save application parameters
(Object 6000h to 6078h )
UNSIGNED32
-
RW
1011
- Restore parameters
ARRAY
-
-
0 Number of entries
Number of subindexes
UNSIGNED8
-
R
1 Restore default values
to all Parameters
Restore all default parameters
same as H03=1 (*3)
UNSIGNED32
-
RW
2
Restore default values
to communication
parameters
Communication parameters are initialized to
the factory default values. (Object 1000h to
1A02h)
UNSIGNED32
-
RW
3 Restore application
parameters
Application parameters are initialized to the
factory default values. (Objject 6000h to
6078h )
UNSIGNED32
-
RW
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......