![Fuji Electric FRENIC-Ace series User Manual Download Page 640](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846640.webp)
11.9 Power Regenerative PWM Converters, RHC Series
11-36
11.9.3 Function specifications
■
Terminal functions
Cl
as
si
fi
-c
ati
on
Symbol
Name
Functions
M
ai
n c
irc
ui
t
L1/R, L2/S, L3/T Main circuit power
inputs
Connects with the three-phase input power lines through a dedicated
reactor.
P(+), N(-)
Converter outputs
Connects with the power input terminals P(+) and N(-) on an inverter.
ok
Grounding
Grounding terminal for the converter’s chassis (or enclosure).
R0, T0
Auxiliary power input for
the control circuit
For the backup of the control circuit power supply, connect the power lines
same as that of the main power input.
Vol
tage
detec
tion R1, S1, T1
Synchronous power
input for voltage
detection
Voltage detection terminals for the internal control of the converter. Connect
with the power supply side of the dedicated reactor or filter.
R2, T2
Inputs for control
monitoring
Detection terminal for AC fuse blown.
Input s
ignal
[RUN]
Run command
Short-circuiting terminals [RUN] and [CM] runs the converter; opening them
stops the converter.
[RST]
Reset alarm command
When the converter stops due to an alarm, removing the alarm factor and
short-circuiting the terminals [RST] and [CM] cancels the protective
function, restarting the converter.
[X1]
General-purpose
transistor input
0: Enable external alarm trip
THR
1: Cancel current limiter
LMT-CCL
2: 73 answerback
73ANS
3: Switch current limiter
I-LIM
4: Option DI
OPT-DI
[CM]
Digital input common
Common terminal for digital input signals.
[PLC]
PLC signal power
Connects to PLC output signal power supply. (Rated voltage: 24 VDC (22 to
27 VDC)
O
utput s
ignal
[30A/B/C]
Alarm relay output
(for any alarm)
Outputs a signal when the protective function is activated to stop the
converter.
(Contact: [1C], Terminals [30A] and [30C] are closed: Signal ON) (Contact
rating: 250 VAC, max. 50 mA)
[Y1], [Y2], [Y3],
[Y11] to [Y18]
General-purpose
transistor output
0: Converter running
RUN
1: Converter ready to run
RDY
2: Power supply current limiting
IL
3: Lifetime alarm
LIFE
4: Heat sink overheat early warning
PRE-OH
5: Overload early warning
PRE-OL
6: Power running
DRV
7: Regenerating
REG
8: Current limiting early warning
CUR
9: Restarting after momentary power failure
U-RES
10: Synchronizing power supply frequency
SY-HZ
11: Alarm content 1
AL1
12: Alarm content 2
AL2
13: Alarm content 4
AL4
14: Option DO
OPT-DO
* Mounting the OPC-VG7-DIOA option makes 8 points of DO extended
functions available. (DI functions are not available.)
[CME]
Digital output common
[Y5A/C]
Relay output
[A01], [A04],
[A05]
General-purpose
analog output
0: Input power
PWR
1: Input current in RMS
I-AC
2: Input voltage in RMS
V-AC
3: DC link bus voltage
V-DC
4: Power supply frequency
FREQ
5: +10 V test
P10
6: -10 V test
N10
* Mounting the OPC-VG7-AIO option makes 2 points of AO extended
functions available. (AI functions are not available.)
[M]
Analog output common Common terminal for analog output signal.
[73A], [73C]
Charging resistor input
relay outputs
Control output for the input relay of the external charging resistor (73).
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......