5.3 Description of Function Codes
5-70
■
Restart mode after momentary power failure (Allowable momentary power failure time) (H16)
Sets the maximum time from when momentary power failure (undervoltage level) occurs until restart (setting
range: 0.0 to 30.0 s). Set coast to a stop time which is allowable for machine and equipment. Momentary power
failure restart operation should be performed within the specified time, however, if the set time is exceeded, the
inverter judges the state as a power shut down, and then operates as powering on again without performing
momentary power failure restart operation.
When allowable momentary power failure time (H16) is set to “999”, momentary power failure restart is performed
until DC link bus voltage decreases by momentary power failure restart allowance voltage (50 V for 200 V class,
100 V for 400 V class), however, if the voltage becomes at or below the momentary power failure allowance
voltage, the state is judged as a power shut down. As a result, the inverter operates as powering ON again without
performing momentary power failure restart operating.
Power supply voltage
Allowance voltage of momentary power failure restart
200V
50V
400V
100V
The time until voltage decreases to the momentary power failure restart allowance voltage from
undervoltage differs greatly depending on the inverter capacity and with/without option.
Power restoration
Power failure
DC link bus
voltage
Undervoltage level
Power failure
period
Preparation time:
approx. 0.3 to 0.6 s
Preparation complete
Gate command ON
Inverter
status
Run command
(case 1)
Run command
Restart
(case 2)
Normal operation start
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......