5.3 Description of Function Codes
5-77
FU
NCT
IO
N
C
O
DE
S
Chap 5
F23 to F25 Starting frequency 1, Starting frequency 1 (Holding time) and Stop frequency
Related function codes:
F38 and F39 (Stop frequency, Detection mode and Holding time)
d24 (Zero speed control)
Under V/f control
At the startup of an inverter, the initial output frequency is equal to the starting frequency. The inverter stops its
output when the output frequency reaches the stop frequency. Set the starting frequency to a level at which the
motor can generate enough torque for startup. Generally, set the rated slip frequency of the motor as the starting
frequency.
Specifying the holding time for the starting frequency compensates for the delay time for the establishment of a
magnetic flux in the motor; specifying that for the stop frequency stabilizes the motor speed at the stop of the
inverter.
■
Starting frequency 1 (F23)
F23 specifies the starting frequency at the startup of an inverter.
•
Data setting range: 0.0 to 60.0 (Hz)
Under V/f control, even if the start frequency is set at 0.0 Hz, the inverter starts its output at 0.1 Hz.
■
Starting frequency 1 (Holding time) (F24)
F24 specifies the holding time for the starting frequency 1.
•
Data setting range: 0.00 to 10.00 (s)
■
Stop frequency (F25)
F25 specifies the stop frequency at the stop of the inverter.
•
Data setting range: 0.0 to 60.0 (Hz)
Under V/f control, even if the stop frequency is set at 0.0 Hz, the inverter stops its output at 0.1 Hz.
■
Stop frequency (Holding time) (F39)
F39 specifies the holding time for the stop frequency.
•
Data setting range: 0.00 to 10.00 (s)
If the starting frequency is lower than the stop frequency, the inverter does not output any power as long
as the reference frequency does not exceed the stop frequency.
Output frequency
Starting frequency 1
(holding time)
Starting
frequency 1
Stop frequency
(holding time)
Stop frequency
Inverter
operation status
Shut off
(gate OFF)
Inverter in operation (gate ON)
Shut off
(gate OFF)
Time
Time
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......