![Fuji Electric FRENIC-Ace series User Manual Download Page 184](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846184.webp)
5.2 Function Codes Table
5-14
Code
Name
Data setting range
C
han
ge
w
hen
ru
nni
ng
D
at
a
co
py
in
g
Factory
Default
Drive control
R
el
at
ed
p
ag
e
V
/f
PG
V/
f
w
/ P
G
To
rq
ue c
on
tro
l
PM
C41 Analog input adjustment
(Terminal [C1] (V2 function))
(Offset)
-5.0 to 5.0%
Y* Y
0.0
Y Y Y Y Y
C42
(Gain) 0.00 to 200.00%
Y* Y
100.0
Y Y Y Y Y
C43
(Filter) 0.00 to 5.00 s
Y Y
0.05
Y Y Y Y Y
C44
(Gain base point) 0.00 to 100.00%
Y* Y
100.0
Y Y Y Y Y
C45
(Polarity selection) 0: Bipolar
1: Unipolar
N Y
1
Y Y Y Y Y
C50 Bias (for frequency setting 1)
(Bias base point)
0.00 to 100.00%
Y* Y
0.00
Y Y Y N Y 5-146
C53 Selection of normal/inverse
operation
(Frequency setting 1)
0: Normal
1: Inverse
Y Y
0
Y Y Y N Y 5-146
C55 Analog input adjustment
(Terminal 12)
(Bias)
-100.00 to 100.00%
Y Y
0.00
Y Y Y Y Y 5-144
C56
(Bias base point) 0.00 to 100.00 %
Y Y
0.00
Y Y Y Y Y
C58
(Display unit) * Same as J105 (However, setting range is, 1 to 80)
Y Y
2
Y Y Y Y Y 5-147
C59
(Maximum scale) -999.00 to 0.00 to 9990.00
N Y
100
Y Y Y Y Y 5-147
C60
(Minimum scale) -999.00 to 0.00 to 9990.00
N Y
0.00
Y Y Y Y Y
C61 Analog input adjustment
(Terminal[C1](C1 function))
(Bias)
-100.00 to 100.00 %
Y Y
0.00
Y Y Y Y Y 5-144
C62
(Bias base point) 0.00 to 100.00 %
Y Y
0.00
Y Y Y Y Y
C64
(Display unit) * Same as J105 (However, setting range is, 1 to 80)
Y Y
2
Y Y Y Y Y 5-147
C65
(Maximum scale) -999.00 to 0.00 to 9990.00
N Y
100
Y Y Y Y Y 5-147
C66
(Minimum scale) -999.00 to 0.00 to 9990.00
N Y
0.00
Y Y Y Y Y
C67 Analog input adjustment
(Terminal [C1] (V2 function))
(Bias)
-100.00 to 100.00 %
Y Y
0.00
Y Y Y Y Y 5-144
C68
(Bias base point) 0.00 to 100.00 %
Y Y
0.00
Y Y Y Y Y
C70
(Display unit) * Same as J105 (However, setting range is,1 to 80)
Y Y
2
Y Y Y Y Y 5-147
C71
(Maximum scale) -999.00 to 0.00 to 9990.00
N Y
100
Y Y Y Y Y 5-147
C72
(Minimum scale) -999.00 to 0.00 to 9990.00
N Y
0.00
Y Y Y Y Y
C89 Frequency correction 1 by
(Numerator)
-32768 to 32767 (Keypad display is 8000 to 7FFFH)
(Interpreted as 1 when the value is set to 0)
Y Y
0001
Y Y Y N Y —
C90 Frequency correction 2 by
(Denominator)
-32768 to 32767 (Keypad display is 8000 to 7FFFH)
(Interpreted as 1 when the value is set to 0)
Y Y
0001
Y Y Y N Y —
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......