E L C O p e r a t i o n M a n u a l
For more information visit:
w w w. e a t o n . c o m
MN05003006E
1-34
Output Point Wiring
Y0
LED
C0
TRANSISTOR OUTPUT
LOAD
ELC-**-**NN*T
< 0.5A
T
ri
gger
ci
rc
ui
t
1. ELC-PH series has only transistor outputs. See “Function Specifications” for their
additional information.
2. When output points are enabled, their corresponding indicators on the front panel will be
on.
3. Isolation circuit: The optical coupler is used to isolate signals between the circuit inside
ELC and input modules.
The Transistor Output Circuit Wiring
MC1
2
3
1
C0 Y0
Y1 C2 Y10 C3 Y11
4
5
3
4
C1
1. DC power supply
2. Emergency stop
3. Circuit protection fuse
4. Flywheel diode + inductive load
5. Manually exclusive output *1
*1: Transistor outputs use internal zener diode (39V) as protection circuitry. When driving the
inductive load with transistor output, a reverse-current protection diode can be installed in
parallel with the load if necessary.
The reverse-current protection diode needs to satisfy the following specifications.
- The diode is rated for maximum reverse voltage of 5 to 10 times the load voltage.
- The forward current is more than the load current.
ELC-PV
Input wiring
There are 2 types of DC inputs, SINK and SOURCE. (Below is an example. For additional