Average function
Configure using CR#2 ~ CR#5.
Range for ELC-TC04ANNN: K1 ~ K100.
Self-diagnosis
Upper and lower limit detection/channel
Communication mode
(RS-485)
ASCII/RTU mode.
Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 bps.
ASCII data format: 7-bit, Even parity, 1 stop bit (7, E, 1),
RTU data format: 8-bit, Even parity, 1 stop bit (8, E, 1).
RS-485 cannot be used when connected to an ELC controller.
When connected to an
ELC controller
The modules are numbered from 0 to 7 based on their position with respect
to the controller.. 0 is the closest to controller and 7 is the furthest. A
maximum of 8 special modules are allowed per controller.
Temperature mode: °C
+6,000
+3,000
-2,000
+600
- 20 0
C
+300
Di gital outpu t
Measured temperatur e input
C
Temperature/digital curve
Temperature mode: °F
+11,120
+5,560
-3,280
+1,112
-328
F
+556
Digi tal outpu t
Measured temperature input
F
Electrical Specifications
Max. rated power
consumption
24 VDC(20.4VDC~28.8VDC) ( –15
%~
+20
%
), 2W, supply from external
power
Noise Immunity
ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & Communication I/O: 1KV
RS(IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m
Grounding
The diameter of the ground wire cannot be smaller than the wire used for the
connections to the 24V and 0V terminals.
Vibration/Shock Immunity
International Standard Regulations: IEC61131-2, IEC 68-2-6 (TEST Fc)/
IEC61131-2 & IEC 68-2-27 (TEST Ea)
Operation/storage
temperature
Operation: 0°C ~55°C (temperature), 50~95% (humidity), pollution degree:
2; Storage: -25°C ~70°C (temperature), 5~95% (humidity)
Agency Approvals
UL508
UL1604, Class1,Div2 Operating temperature code: T5
European community EMC Directive 89/336/EEC and Low Voltage Directive
73/23/EEC