w w w. e a t o n . c o m
1-35
Digital/Analog (D/A)
Voltage output
Current output
Protection
The voltage output is protected from short circuit. Also be aware that a short
circuit condition existing for too long of a time may cause damage on internal
circuits. The current output can be open circuit.
Communication mode
(RS-485)
ASCII/RTU mode.
Communication baud rates available:
4,800/9,600/19,200/38,400/57,600/115,200 bps. ASCII data format: 7-bit,
Even, 1 stop bit (7, E, 1).
RTU data format: 8-bit, Even, 1 stop bit (8, E, 1).
RS-485 cannot be used when connected to ELC MPU in series.
When connected to
ELC MPU in series
The modules are numbered from 0 to 7 with respect to their position from from
the controller. 0 is the closest to the controller and 7 is the furthest. Max. 8
modules are allowed per controller and they do not count agains the allowable
digital I/O.
Mode 0: (0V ~ +10V), Mode 1: (2V ~ +10V)
10V
+4, 000
0
OFFSET
6V
5V
2V
GAI N
+2, 000
Voltage output
Mode 1
Mode 0
Digita l input
Conversion
characteristic curve
(default setting is 0)
Mode 2: (4mA ~ +20 mA), Mode 3: (0mA ~ +20mA)
20mA
+4, 000
0
OFFSET
4mA
GAIN
+2, 000
12mA
10mA
Current output
Mode 2
Mode 3
Digital input
Electrical Specifications
Max. rated power
consumption
24 VDC(20.4VDC~28.8VDC) ( –15
%~
+20
%
), 2W, supply from external power
Noise Immunity
ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV, Analog &
Communication I/O: 1KV
RS(IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m
Grounding
The diameter of the ground wire cannot be smaller than that of the wire used for
the 24V and 0V connections.
Vibration/Shock
Immunity
International Standard Regulations: IEC61131-2, IEC 68-2-6 (TEST Fc)/
IEC61131-2 & IEC 68-2-27 (TEST Ea)
Operation/storage
temperature
Operation: 0°C ~55°C (temperature), 50~95% (humidity), pollution degree: 2;
Storage: -25°C ~70°C (temperature), 5~95% (humidity)