Register content
Description
#20 X R
Present temperature measured
at CH1
#21 X R
Present temperature measured
at CH2
#22 X R
Present temperature measured
at CH3
#23 X R
Present temperature measured
at CH4
Present temperature measured at CH1 ~ CH4
Temperature units: set in CR#7
#28 O R/W Adjusted Offset value of CH1
#29 O R/W Adjusted Offset value of CH2
#30 O R/W Adjusted Offset value of CH3
#31 O R/W Adjusted Offset value of CH4
Set the adjusted Offset value for Ch1 ~ Ch4. Default
= K0
Range: K-400 ~ K400
Temperature unit: set in CR#7
Definition of Offset at Ch1 ~ Ch4 in
ELCM-TC04ANNN: Deviation of the digital value
from the target value.
#40 O R/W
Function: Prohibit configuration
changes
Prohibit configuration changes for CH1 ~ CH4
#41 X R/W
Function: Save all configuration
values
Save all configuration values, Default =H’0000
#42 X R/W
Function: Return to default
setting
Set all values to default settings, Default = H’0000
#43 X R Error
status
Register for storing all error status. See the table of
error status for more information.
#100 O R/W
Function: Enable / Disable limit
detection
Enable / Disable the upper and lower limit detection
function. Default= H’0000.
#101 X R/W Upper and lower limit status
Display the upper and lower limit values, Default
=H’0000
#102 O R/W Set value for CH1 upper limit
#103 O R/W Set value for CH2 upper limit
#104 O R/W Set value for CH3 upper limit
#105 O R/W Set value for CH4 upper limit
Set upper limit values for CH1~CH4. Default =
K32000.
#108 O R/W Set value for CH1 lower limit
#109 O R/W Set value for CH2 lower limit
#110 O R/W Set value for CH3 lower limit
#111 O R/W Set value for CH4 lower limit
Set lower limit values for CH1~CH4. Default =
K-32000.
y
PID Control Registers
CR#
CH1 CH2 CH3 CH4
Save
Register content
Description
#120 #140 #160 #180 O R/W
Set temperature
value
Set the temperature value according to
proper range for each sensor type. Default =
K0
#121 #141 #161 #181 O R/W Sampling time (s)
Range: K1 ~ K30 (s). Default = K2
#122 #142 #162 #182 O R/W K
P
Proportional control constant. Default = K121
#123 #143 #163 #183 O R/W K
I
Integral constant. Default = K2,098