E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-66
ELC-TC04ANNN
EXPLANATION
bit
CR
No
Param.
Comm.
Add.
Latched
Register Name
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
#10 H’40A0 X R
CH1 average degrees
(°F)
#11 H’40A1 X R
CH2 average degrees
(°F)
#12 H’40A2 X R
CH3 average degrees
(°F)
#13 H’40A3 X R
CH4 average degrees
(°F)
Average degrees for channels CH1~CH4.
(unit: 0.1 degrees F)
#14 H’40A4 X R
Present temp. of CH1
(°C)
#15 H’40A5 X R
Present temp. of CH2
(°C)
#16 H’40A6 X R
Present temp. of CH3
(°C)
#17 H’40A7 X R
Present temp. of CH4
(°C)
Present temperature for channels CH1~CH4.
(unit: 0.1 degrees C)
#19 H’40A9 X R
Present temp. of CH1
(°F)
#20 H’40AA X R
Present temp. of CH2
(°F)
#21 H’40BB X R
Present temp. of CH3
(°F)
#22 H’40BC X R
Present temp. of CH4
(°F)
Present temperature for channels CH1~CH4.
(unit: 0.1degrees F)
#24 H’40AE O R/W CH1 OFFSET Value
#25 H’40AF O R/W CH2 OFFSET Value
#26 H’40B0 O R/W CH3 OFFSET Value
#27 H’40B1 O R/W CH4 OFFSET Value
Adjust offset value of channels CH1~CH4. The range is
-1,000~+1,000 and factory setting is K0.
(unit: 0.1 degrees C)
#30 H’40B4 X R Error status
Data register stores the error status; refer to fault code
chart for details.
#31 H’40B5 O R/W
Communication
address setting
RS-485 communication address.
Setting range is 01~255 and factory setting is K1
#32 H’40B6 O R/W
Communication baud
rate setting
Communication baud rate (4,800, 9,600, 19,200, 38,400,
57,600 and 115,200 bps).
b0: 4,800 bps (bit/sec).
b1: 9,600 bps (bit/sec). (factory setting)
b2: 19,200 bps (bit/sec). b3: 38,400 bps (bit/sec).
b4: 57,600 bps (bit/sec). b5: 115,200 bps (bit/sec).
b6~b13: Reserved.
b14: switch between low byte and high byte of CRC code
(only for RTU mode)
b15: RTU mode.