3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-65
3.1.5.6 Terminal
Layout
L+
L-
S LD
C
H
1
L+
L-
C
H
2
E
L
C-
T
C
04
A
NNN
L+
L-
S LD
C
H
3
L+
L-
S LD
C
H
4
SL D
L+
L-
SLD
L+
L-
SLD
L+
L-
SLD
L+
L-
SLD
3.1.5.7 CR
(Control
Registers)
ELC-TC04ANNN
EXPLANATION
bit
CR
No
Param.
Comm.
Add.
Latched
Register Name
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
#0 H’4096 O
R Module type
System used, data length is 8bits (b7~b0).
ELC-TC04ANNN module code = H’8B
Reserved CH4 CH3 CH2 CH1
#1 H’4097 O R/W Thermocouple type
Example: Configuring CH1
1. (b2~b0) set (0,0,0) to use J type.
2. (b2~b0) set (0,0,1) to use K type.
3. (b2~b0) set (0,1,0) to use R type.
4. (b2~b0) set (0,1,1) to use S type.
5. (b2~b0) set (1,0,0) to use T type.
#2 H’4098 O R/W
CH1 average number
of samples
#3 H’4099 O R/W
CH2 average number
of samples
#4 H’409A O R/W
CH3 average number
of samples
#5 H’409B O R/W
CH4 average number
of samples
The number of samples used for “average” temperature
on channels CH1~CH4.
Range is K1~K100 and factory setting is K10.
#6 H’409C X
R
CH1 average degrees
(°C)
#7 H’409D X
R
CH2 average degrees
(°C)
#8 H’409E X
R
CH3 average degrees
(°C)
#9 H’409F X
R
CH4 average degrees
(°C)
Average degrees for channels CH1~CH4.
(unit: 0.1 degrees C)