6-4
Wiring
y
Please use O-type or Y-type terminals for I/O wiring terminals. The specification for the
terminals is as shown on the right. Use Copper Conductor Only, 60 °C.
y
Tighten ELC terminal screws to a torque of 5 to 8 kg-cm (4.3~6.9 in-lbs).
To suit M3.5 screw terminals
Below 6.2
Below 6.2
NOTICE:
y
Connect the AC input (100VAC ~ 240VAC) to terminals L and N. Any AC110V or AC220V
connected to the +24V terminal will permanently damage the ELC-PS01/PS02.
y
Please use wires of 1.6mm and above for the grounding.
y
If the power-cut time is less than 10ms, the ELC-PS01/PS02 still operates unaffectedly. If
the power-cut time is too long, the ELC-PS01/PS02 will stop operating and all the
outputs will be Off.