Average function
Supported. Available for setting up sampling range in CR#8 ~ CR#11. Range: K1
~ K100.
Self-diagnosis
Upper and lower bound detection in all channels
Series connection to
ELCM MPU
The modules are numbered from 0 to 7 distancebased on their position with
respect to the controller. Max. 8 modules are allowed per controller
Mode 0 (H’0000): (-10V ~ +10V)
Voltage input
+32000
+16000
-16000
10V
-32000
-10V
5V
0
Gain
Offset
Digital
output
+32384
-32384
Mode 1 (H’0001): (-5V ~ +5V)
Voltage input
+32000
+16000
-16000
5V
-32000
-5V
2.5V
0
Gain
Offset
Digital
output
+32384
-32384
A/D conversion curve
(Default: mode 0)
Mode 2 (H’0002): (0V~+10V)
Voltage input
+32000
+16000
10V
5V
0
Gain
Offset
Digital
output
+32384
-384
Mode 3 (H’0003): (0V~+5V)
Voltage input
+32000
+16000
5V
2.5V
0
Gain
Offset
Digital
output
+32384
-384
Mode 4 (H’0004): (-20mA~ +20mA)
+32000
+16000
-16000
20mA
-32000
-20mA
10mA
0
Gain
Offset
Digital
output
Current input
+32384
-32384
Mode 5 (H’0005): (0 ~ +20mA)
+32000
+16000
20mA
10mA
0
Gain
Offset
Digital
output
Current input
+32384
-384
A/D conversion curve
(Default: mode 0)
Mode 6 (H’0006): (+4mA ~ +20mA)
+32000
4mA
0
Offset
20mA
12mA
Gain
+16000
Digital
output
Current input
+32384
-384
Mode -1 (H’FFFF): Channel
unavailable. Average value and present
value of input channels will be
displayed as 32,767(H’7FFF).