V+
I+
COM
F G
0mA~20mA
CH1
CH1
Current output
Shielded c abl e
AC motor driv e,
rec or der,
sc al e valv e...
4. Program
Description
y
When the ELC goes from STOP to RUN, set CH1 to current output mode (mode 3).
y
In the current mode for the ELC-AN04NANN, the range for 0 ~ 20mA is K0 ~ K4,000.
D0 is the current output value in ma, which is 1/200 of the actual output current digital
value (i.e. 20/4,000 = 1/200). Multiply the value in D0 by 200 and store the value
obtained into data register D40, which is sent to the ELC-AN04NANN for analog
output channel CH1.
5. Example
program
Ladder diagram:
Explanation:
Set CH1 to mode 3 (current
output mode)
D0 is the current output value
for CH1
D40 is the corresponding
digital value of the output
current for CH1
M1002
M1000
END
K0
K1
TO
D0
K200
K6
K1
K0
K1
H3
MUL
D40
TO
D40