E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-20
External Wiring
V+
I+
COM
V+
I+
COM
24+
24-
DC/DC
+15V
-15V
AG
FG
FG
CH1
CH1
0V~+10V
*2
*3
DC24V
CH4
CH4
AC drive, recorder,
scale valve...
AC drive, recorder,
scale valve...
Voltage output
shielding cable *1
shielding cable *1
Current output
converter
terminal of
power module
System
grounding
Class 3 grounding
(100
or less)
.
.
.
.
.
Note 1
: Isolate analog output and power wiring.
Note 2
: To avoid electrical noise issues, connect a 0.1~0.47
μ
F 25V capacitor for noise filtering.
Note 3
: Connect
power module terminal and
analog output module terminal to system
earth ground.
Warning
: DO NOT wire to the No function terminals.