E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-6
3.1.1.6 Terminal
Layout
FG
V+
I+
COM
C
H
1
FG
V+
I+
COM
C
H
2
E
L
C-
A
N
0
4
A
NNN
FG
V+
I+
COM
C
H
3
FG
V+
I+
COM
C
H
4
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
3.1.1.7 CR
(Control
Register)
ELC-AN04ANNN
EXPLANATION
bit
CR
No
Param.
Comm.
Add.
Latched
Register Name
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
#0 H’4000 O R Module
type
System used, data length is 8bits (b7~b0).
ELC-AN04ANNN model code =H’88
Reserved CH4 CH3 CH2 CH1
#1 H’4001 O R/W
Configuration word
for the analog input
channels
Input mode: factory setting is H0000.
Mode 0: voltage mode (-10V~+10V).
Mode 1: voltage mode (-6V~+10V).
Mode 2: current mode (-12mA~+20mA)
Mode 3: current mode (-20mA~+20mA)
Mode 4: Reserved.
#2 H’4002 O R/W CH1 average number
#3 H’4003 O R/W CH2 average number
#4 H’4004 O R/W CH3 average number
#5 H’4005 O R/W CH4 average number
Number of samples used for calculating average analog
input values for channels CH1~CH4. Range is K1~K100
samples and the default setting is K10 samples.
#6 H’4006 X R
Average value of
CH1 input signal
#7 H’4007 X R
Average value of
CH2 input signal
#8 H’4008 X R
Average value of
CH3 input signal
#9 H’4009 X R
Average value of
CH4 input signal
Average values of CH1~CH4 input signals
#12 H’400C X R
Present value of CH1
input signal
#13 H’400D X R
Present value of CH2
input signal
Present values of CH1~CH2 input signals