3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-97
CR#
Attrib.
Register name
Explanation
#5
O R/W CH4 output mode setting
Mode 2 (H’0002): Current output (+4~+20mA)
Mode -1 (H’FFFF): All channels are unavailable
#16 X R/W CH1 output signal value
#17 X R/W CH2 output signal value
#18 X R/W CH3 output signal value
#19 X R/W CH4 output signal value
Voltage output range: K-32,000~K32,000. Current
output range: K0~K32,000.
Default: K0.
CR#18~CR#19 of ELCM-AN02NANN are reserved.
#28 O R/W Adjusted Offset value of CH1
#29 O R/W Adjusted Offset value of CH2
#30 O R/W Adjusted Offset value of CH3
#31 O R/W Adjusted Offset value of CH4
Set the adjusted Offset value of CH1 ~ CH4. Default
= K0
Definition of Offset:
The corresponding voltage (current) input value
when the digital output value = 0
#34 O R/W Adjusted Gain value of CH1
#35 O R/W Adjusted Gain value of CH2
#36 O R/W Adjusted Gain value of CH3
#37 O R/W Adjusted Gain value of CH4
Set the adjusted Gain value of CH1 ~ CH4. Default
= K16,000.
Definition of Gain:
The corresponding voltage (current) input value
when the digital output value = 16,000
#40 O R/W
Function: Set value changing
prohibited
Prohibit configuration changes for CH1 ~ CH4.
Default= H’0000.
#41 X R/W
Function: Save all the set
values
Save all configuration values. Default =H’0000.
#42 X R/W
Function: Return to default
setting
Set all values to default settings. Default = H’0000
#43 X R Error
status
Register for storing all error status. Refer to table
of error status for more information.
#100 O R/W
Function: Enable/Disable limit
detection
Enable/Disable the upper and lower limits
detection function. Default= H’0000.
#101 X R/W Upper and lower limit status
Display the upper and lower limit value. Default
=H’0000.
#102 O R/W Set value of CH1 upper limit
#103 O R/W Set value of CH2 upper limit
#104 O R/W Set value of CH3 upper limit
#105 O R/W Set value of CH4 upper limit
Set value of CH1~CH3 upper limit. Default =
K32000.
#108 O R/W Set value of CH1 lower limit
#109 O R/W Set value of CH2 lower limit
#110 O R/W Set value of CH3 lower limit
#111 O R/W Set value of CH4 lower limit
Set value of CH1~CH4 lower limit. Default =
K-32000.
#114 O R/W Output update time of CH1
#115 O R/W Output update time of CH2
#116 O R/W Output update time of CH3
#117 O R/W Output update time of CH4
Set value of CH1~CH4 lower limit. Default
=H’0000.
#118 O R/W LV output mode setting
Set the output mode of CH1~CH4 when the power
is at LV (low voltage) condition. Default= H’0000.
O: When CR#41 is set to H’5678, the configuration values will be saved.
X: set value will not be saved.
R: able to read data by using FROM instruction.
W: able to write data by using TO instruction.