E L C O p e r a t i o n M a n u a l
For more information visit:
w w w. e a t o n . c o m
MN05003006E
1-32
1. DC power supply
2. Emergency stop
3. Circuit protection fuse
4. Flywheel diode + inductive load
5. Manually exclusive output *1
*1: Transistor outputs use internal zener diode (39V) as protection circuitry. When driving the
inductive load with transistor output, a reverse-current protection diode can be installed in
parallel with the load if necessary.
The reverse-current protection diode needs to satisfy the following specifications.
- The diode is rated for maximum reverse voltage of 5 to 10 times the load voltage.
- The forward current is more than the load current.
ELC-PA
Input Wiring
There are 2 types of DC inputs, SINK and SOURCE. (Below is an example. For additional
information, refer to the specifications for each module.)
z
DC Signal IN – SINK mode
Input circuit
+24V 0V
DC Power Supply
S/S
X0
X1
X2
Sink mode
z
DC Signal IN – SOURCE mode
Input circuit
+24V 0V
DC Power Supply
S/S
X0
X1
X2