1 . M P U U n i ts
MN05003006E For more informat ion visit :
w w w. e a t o n . c o m
1-73
Model
L
L1
ELCB-PB10NNDR/T
ELCB-PB14NNDR/T
ELCB-PB16NNDR/T
95 86
ELCB-PB20NNDR/T
ELCB-PB24NNDR/T
ELCB-PB30NNDR/T
ELCB-PB32NNDR/T
150 141
ELCB-PB40NNDR/T
164 155
1.4.3 Installation
and
Wiring
1.4.3.1 Installation
Install the ELC in an enclosure with sufficient space around it to allow heat dissipation, as shown in
the figure below.
z
DIN Rail Mounting:
The ELC can be secured to a cabinet by using 35mm height and 7.5mm
in depth DIN rail. When mounting the ELC to 35mm DIN rail, be sure to use the retaining clip to
stop any side-to-side movement of the ELC and reduce the chance of wires coming loose. The
retaining clip is at the bottom of the ELC. To secure the ELC to DIN rail, pull the clip down,
place it onto the rail and push the clip back up. To remove the ELC, pull the retaining clip down
with a flat screwdriver and remove the ELC from the DIN rail.
z
Direct Mounting:
Use M4 screws according to the dimension of the product.
1.4.3.2 Terminal
Torque
1. Use the 12-24 AWG single-core wire or the multi-core wire for the I/O wiring. The ELC terminal
screws should be tightened to 3.80 kg-cm (3.30 in-lbs) and use 60/75°C copper conductor
only.
24-12AWG
< 1.5mm