When CH1 is configured for mode 1 (H’0001) CR#2 must be set to H’0001. The default
setting = H’0000. CH1 example:
Mode 0 (H’0000): PT100 (-180°C ~ 800°C).
Mode 1 (H’0001): NI100 (-80°C ~ 170°C).
Mode 2 (H’0002): PT1000 (-180°C ~ 800°C).
Mode 3 (H’0003): NI1000 (-80°C ~ 170°C).
Mode 4 (H’0004): 0~300
Ω
.
Mode-1 (H’FFFF): Channel 1 unavailable.
C R # 7 :
Temperature units
Select the temperature units for average temperature and present temperature. (Celsius °C /
Fahrenheit °F). Default = H’0000.
Mode 0 (H’0000): Celsius °C.
Mode 1 (H’0001): Fahrenheit °F.
C R # 8 , 9 , 1 0 , 11 :
CH1 ~ CH4 number of samples
1. The number of samples used for the average temperature values for CH1 ~ CH4.
2. Range: K1 ~ K100. Default = K10. If the value exceeds K100, the value will be set to
K100; if the value is less than K1, it will be set to K1.
C R # 1 2 , 1 3 , 1 4 , 1 5 :
Average temperature measured at CH1 ~ CH4
The average temperature measured at CH1 ~ CH4. These values are calculated based on
the number of samples set in CR#8 ~ CR#11. Temperature units: set in CR#7. For example, if
the sampling range is set as K10, the contents in CR#12 ~ CR#15 will be the average of the
most recent 10 temperature signals in CH1 ~ CH4.
C R # 2 0 , 2 1 , 2 2 , 2 3 :
Present temperature measured at CH1 ~ CH4
The present temperature at CH1 ~ CH4. Temperature units: set in CR#7.
C R # 2 8 , 2 9 , 3 0 , 3 1 :
Adjusted Offset value for CH1 ~ CH4
1. Set the adjusted Offset value for CH1 ~ CH4
2. Range:
K-400~K400
3. Default setting = K0
Mode 0 ~ Mode 3:
Equation:
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛
−
°
°
=
Offset
X
Y
)
(
1
.
0
)
(