3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-93
ELCM-AN02NANN
ELCM-AN04NANN
Voltage output
Current output
Range of digital
conversion
-32,000 ~ +32,000
0 ~ +32,000
0 ~ +32,000
Max./Min. input range
of digital data
-32,768 ~ +32,767
0 ~ +32,767
-6,400 ~ +32,767
Resolution
14 bits
20V/64000
14 bits
20mA/32000
14 bits
16mA/32000
Output impedance
0.5
Ω
or less
Overall accuracy
±
0.5% when in full scale (25°C, 77°F);
±
1% when in full scale within the range of (0 ~ 55°C, 32 ~ 131°F)
Response time
3 ms/ all channels
Max. output current
20mA (1K
Ω
~ 2M
Ω
) -
Tolerance load
impedance
-
0 ~ 500
Ω
Digital data format
16 significant bits out of 16 bits are available; in 2’s complement
Isolation
Optical coupler isolation between analog circuits and digital circuits. No
isolation among analog channels.
500VDC between digital circuits and Ground
500VDC between analog circuits and Ground
500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground
Protection
Voltage output is protected from short circuits. However, short circuit
conditions lasting for too long may cause damage to the internal circuits.
Current output can be open circuit.
Series connection to
ELCM controllers
The modules are numbered from 0 to 7 based on their position with respect to
the controller. Max. 8 modules are allowed per controller
Mode 0 (H’0000): (-10V ~ +10V)
10V
+3 2,000
0
Offset
5V
Gai n
+1 6,000
Voltage
output
D igital input
-10 V
-5V
-32 ,0 00
+3 2,767
-32 ,7 68
Mode 1 (H’0001): (0mA ~ +20mA)
20m A
+3 2,000
0
Offs et
Gai n
+1 6,000
10m A
C urren t
output
D igita input
l
+3 2,767
D/A conversion curve
(Default: mode 0)
Mode 2 (H’0002): (+4mA ~ +20 mA)
20m A
+3 2,000
0
Offset
4m A
+1 6,000
12m A
C urren t
outpu t
D igita inpu t
l
Gai n
+3 2,767
-6,40 0
Mode -1 (H’FFFF): Channel
unavailable. The channel is
disabled. Output voltage = 0; output
current = 0.
Operation/storage
1. Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity); pollution degree
2
2. Storage: -25°C ~ 70°C (temperature), 5 ~ 95%
(
humidity
)
Vibration/shock
immunity
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc) / IEC61131-2 & IEC
68-2-27 (TEST Ea)