3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-113
2.
Install the ELC in an enclosure with sufficient space around it to allow heat
dissipation, as shown in the figure below
.
Wiring
1.
Use 22-16 AWG (1.5mm) single-core wire or the multi-core wire for the I/O wiring. The
specification of the terminal is shown in the figure below on the right hand side. The ELC
terminal screws should be tightened to 1.95 kg-cm (1.7 in-lbs). Also, use 60/75°C copper
conductor only.
2.
DO NOT wire empty terminals. DO NOT place the signal wires and power wires in the
same conduit.
3.
DO NOT drop metallic conductors into the ELC during installation.
y
Attach the dustproof sticker to the ELC before installation to prevent conductive objects
from dropping in.
y
Tear off the sticker before running the ELC to ensure normal heat dissipation
.
24-12AWG
< 1.5mm
External Wiring