background image

R7M-SV4

P. 1 / 7

EM-7803-A Rev.6

DC VOLTAGE/CURRENT INPUT MODULE, 4 points

(Modbus)

MODEL

R7M-SV4

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

DC voltage/current input module .......................................(1)
Terminating resistor (110Ω, 0.25W) ...................................(1)

 

MODEL NO.

Confirm that the model number described on the product is
exactly what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.

POINTS OF CAUTION

 

NONINCENDIVE APPROVAL OPTION

• This equipment is suitable for use in Class I, Division 2,

Groups A, B, C, D or Non-Hazardous Locations only.

• WARNING! – Explosion Hazard –

Substitution of any component may impair suitability for
Class I, Division 2.

• WARNING! – Explosion Hazard –
• DO NOT disconnect while the circuit is live or unless the

area is known to be free of ignitable concentrations.

• Temperature Code of this equipment is T5 and the Maxi-

mum Ambient Temperature is 55°C (Surrounding Tem-
perature inside the fire enclosure).

 

CONFORMITY WITH UL APPROVAL

• This equipment is suitable for use in Installation Catego-

ry II and in a Pollution Degree 2 environment.

• Altitude up to 2000 meters.
• This equipment must be mounted inside a suitable fire

enclosure.

• This equipment is to be supplied by a Class 2 power sup-

ply.

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrat-
ed in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.

• Install lightning surge protectors for those wires connect-

ed to remote locations.  Choose a surge protector with its
maximum surge voltage 40V or less between lines.  Rec-
ommended M-System model: MDP-D24.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and

confirm its operational range as indicated below:

24V DC rating: 24V ±10%, approx. 90mA

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the

air, install the unit inside proper housing with sufficient
ventilation.

• Do not install the unit where it is subjected to continuous

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C

(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive

cable, high frequency line, etc.).

• Do not bind these cables together with those in which

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7M-SV4-R

Page 1: ... mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices and connected wires may affect the protection level of this unit when it is integrat ed in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure CE conformity Install...

Page 2: ...tension ON OFF Discrete input 8 or 16 points OFF ON Discrete output 8 or 16 points Conversion Rate Accuracy SW1 3 1 4 SW1 3 SW1 4 CONVERSION RATE ACCURACY OFF OFF 80 msec 0 1 ON OFF 40 msec 0 2 OFF ON 20 msec 0 4 ON ON 10 msec 0 8 Input Range SW1 5 1 6 1 7 1 8 SW1 5 SW1 6 SW1 7 SW1 8 INPUT RANGE OFF OFF OFF OFF 10 10V DC ON OFF OFF OFF 5 5V DC OFF ON OFF OFF 1 1V DC ON ON OFF OFF 0 10V DC OFF OFF ...

Page 3: ...r to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Communication cable Applicable wire size 0 2 to 0 5 mm2 AWG26 22 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Others 0 25 to 1 65 mm2 AWG 22 to 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co ltd 6...

Page 4: ...e both made of metal when installing the R7M Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7M module to the internal panel plate of the control panel Note If electromagneti...

Page 5: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install the R7M Series inside a control panel Attachment part of earth clamp should be fixed with screw ...

Page 6: ...ions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the control panel or close to the I O terminal or connector whichever is more effective Also the imp...

Page 7: ...tus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via Modbus ground the cable shield using an earth clamp Keep the wires away from each other at both ends of the filter 056 222 38 18 mailbox sentronic c...

Reviews: