background image

R7M-SV4

P. 5 / 7

EM-7803-A Rev.6

Use (e.g.) a shield cover 
when noise leaks through 
the opening.

To external apparatus

Keep the opening

for cabling as small as

possible.

Install an electromagnetically
shielded gasket when 
noise leaks through 
the opening.

Shielding is strengthened 
by using an electro-
magnetically shielded 
control panel.

By connecting the
internal panel plate 
and the panel cover with 
an earth strap, grounding 
may be strengthened and
EMC may be improved.

Ground the control panel 

at low impedance using 

 (e.g.) braided wires.

Keep the opening for 

ventilation as small as

posible.

Attach an electro-
magnetically shielded
filter when noise leaks 
through the opening.

Install the R7M Series inside

a control panel.

Attachment part of earth

clamp should be fixed with 

screw in conduction with the

internal panel plate.

• Points of cautions applicable when installing the R7M Series

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7M-SV4-R

Page 1: ... mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices and connected wires may affect the protection level of this unit when it is integrat ed in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure CE conformity Install...

Page 2: ...tension ON OFF Discrete input 8 or 16 points OFF ON Discrete output 8 or 16 points Conversion Rate Accuracy SW1 3 1 4 SW1 3 SW1 4 CONVERSION RATE ACCURACY OFF OFF 80 msec 0 1 ON OFF 40 msec 0 2 OFF ON 20 msec 0 4 ON ON 10 msec 0 8 Input Range SW1 5 1 6 1 7 1 8 SW1 5 SW1 6 SW1 7 SW1 8 INPUT RANGE OFF OFF OFF OFF 10 10V DC ON OFF OFF OFF 5 5V DC OFF ON OFF OFF 1 1V DC ON ON OFF OFF 0 10V DC OFF OFF ...

Page 3: ...r to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Communication cable Applicable wire size 0 2 to 0 5 mm2 AWG26 22 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Others 0 25 to 1 65 mm2 AWG 22 to 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co ltd 6...

Page 4: ...e both made of metal when installing the R7M Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7M module to the internal panel plate of the control panel Note If electromagneti...

Page 5: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install the R7M Series inside a control panel Attachment part of earth clamp should be fixed with screw ...

Page 6: ...ions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the control panel or close to the I O terminal or connector whichever is more effective Also the imp...

Page 7: ...tus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via Modbus ground the cable shield using an earth clamp Keep the wires away from each other at both ends of the filter 056 222 38 18 mailbox sentronic c...

Reviews: