E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-174
Mode 5 of CR#2~ CR#5
-150°C ~ 980°C (-1500~9800)
-238°F ~ 1796°F (-2380~17960)
Offset (CR#34 ~ CR#37)
Offset value
z
Mode 6 (H’0006): N-type,
°C (°F)
+12800(23360)
-1500(-2380)
+1280
-150 C
C
F)
(-238
F)
(+2336
Measured
temperature
input
Digital output
Mode 6 of CR#2~ CR#5
-150°C ~ 1280°C (-1500~12800)
-238°F ~ 2336°F (-2380~23360)
Offset (CR#34 ~ CR#37)
Offset value
z
Mode 7 (H’0007): -80mV~+80mV
+8000
80mV
-8000
-80mV
Digital
output
Voltage input
Mode 7 of CR#2~ CR#5
-80mV~+80mV (-8000~8000)
Offset (CR#34 ~ CR#37)
Offset value
Adjusting the Conversion Curve
1. Description
•
If there is deviation in the measurement results, make adjustments to the Offset
value to modify the conversion curve. For example, if the temperature deviation from
the target temperature (measured temperature) is -2°C, set the Offset of CH1 to 2°C
(2°C /0.1°C = 20).
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛
+
°
°
=
Offset
X
Y
)
C
(
1
.
0
)
C
(
Example: If X= -2
°
C, Y=?