3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-115
3.2.3.6 Terminal
Layout
VI 1
+
I1
V1
+
I3
+
I2
+
V2
V3
+
VI 2
V4
+
VI 3
VI 4
+
I4
+
FE
FE
FE VO1
VO2
AG
IO1
IO2 AG
24 V 0V
3.2.3.7 CR
(Control
Register)
CR#
Attrib.
Register name
Explanation
#0
O
R
Module Type
ELCM-AN06AANN model code = H’00C4
#1
O
R
Firmware version
Display the current firmware version in hex.
#2 O
R/W
CH1
configuration
word
#3 O
R/W
CH2
configuration
word
#4 O
R/W
CH3
configuration
word
#5 O
R/W
CH4
configuration
word
Input mode: Default = H’0000.
CH1 example:
Mode 0 (H’0000):Voltage input (±10V)
Mode 1 (H’0001):Voltage input (±5V)
Mode 2 (H’0002):Voltage input (0 ~+10V)
Mode 3 (H’0003):Voltage input (0 ~+5V)
Mode 4 (H’0004):Current input (±20mA)
Mode 5 (H’0005):Current input (0 ~+20mA)
Mode 6 (H’0006):Current input (4 ~+20mA)
Mode -1 (H’FFFF):Channel 1 unavailable
#6 O
R/W
CH5
configuration
word
#7 O
R/W
CH6
configuration
word
Output mode: Default = H’0000.
CH5 example:
Mode 0 (H’0000):Voltage output (±10V)
Mode 1 (H’0001):Current output (0~+20mA)
Mode 2 (H’0002):Current output (4~+20mA)
Mode -1 (H’FFFF):Channel 5 unavailable
#8
O R/W CH1 number of samples
#9
O R/W CH2 number of samples
#10
O R/W CH3 number of samples
#11
O R/W CH4 number of samples
Set the number of samples for CH1 ~ CH4:
Range = K1 ~ K100
Default = K10
#12
X
R
CH1 average input value
#13
X
R
CH2 average input value
#14
X
R
CH3 average input value
#15
X
R
CH4 average input value
Average value of analog inputs for CH1 ~ CH4
#16
X R/W CH5 output signal value
#17
X R/W CH6 output signal value
Analog outputs: Voltage output range:
K-32,000~K32,000. Current output range:
K0~K32,000. Default: K0.
#20
X
R
CH1 present input value
#21
X
R
CH2 present input value
#22
X
R
CH3 present input value
#23
X
R
CH4 present input value
Present value of analog inputs at CH1 ~ CH4