3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-39
ELC- AN06AANN
EXPLANATION
bit
CR
No
Param.
Comm.
Add.
Latched
Register Name
15 14 13 12 11 10 9
8 7 6 5 4 3 2 1 0
#20 H’40DC O R/W
To adj. Offset value of
CH3
#21 H’40DD O R/W
To adj. Offset value of
CH4
Offset setting for CH3~CH4. Factory setting is K0 and unit
is LSB.
Voltage input: range is K-1,000 ~K1,000
Current input: range is K-1,000 ~K1,000
#22 H’40DE O R/W
To adj. Offset value of
CH5
#23 H’40DF O R/W
To adj. Offset value of
CH6
Offset setting for CH5~CH6. Factory setting is K0 and unit
is LSB.
The range is K-2,000~K2,000
#24 H’40E0 O R/W
To adj. GAIN value of
CH1
#25 H’40E1 O R/W
To adj. GAIN value of
CH2
#26 H’40E2 O R/W
To adj. GAIN value of
CH3
#27 H’40E3 O R/W
To adj. GAIN value of
CH4
GAIN setting for CH1~CH4. Factory setting is K1,000 and
unit is LSB.
Voltage input: range is K-800 ~K4,000
Current input: range is K-800 ~K2,600
#28 H’40E4 O R/W
To adj. GAIN value of
CH5
#29 H’40E5 O R/W
To adj. GAIN value of
CH6
GAIN setting for CH5~CH6. Factory setting is K2,000 and
unit is LSB.
The range is K-1,600~K8,000
#30 H’40E6 X
R Error status
Data register stores the error status, refer to fault code
chart for details.
#31 H’40E7 O R/W
Communication
address setting
RS-485 communication address.
The range is K1~K255 and factory setting is K1
#32 H’40E8 O R/W
Communication baud
rate setting
Communication baud rate (4,800, 9,600, 19,200, 38,400,
57,600 and 115,200 bps).
For ASCII mode, data format is 7 Bits, even parity, 1 stop
bit (7,E,1). For RTU mode, data format is 8 Bits, even
parity, 1 stop bit (8, E, 1).
b0: 4,800 bps (bit/sec)
b1: 9,600 bps (bit/sec). (factory setting)
b2: 19,200 bps (bit/sec)
b3: 38,400 bps (bit/sec)
b4: 57,600 bps (bit/sec)
b5: 115,200 bps (bit/sec)
b6~b13: Reserved
b14: switch between low byte and high byte of CRC code
(only for RTU mode)
b15: RTU mode