ELC-PV
Items
Specifications
Remarks
Control method
Stored program, cyclic scan system
I/O processing method
Batch processing method (when END
instruction is executed)
Fast I/O refresh
instruction can
override batch update
Execution speed
Basic instructions – 0.24
μ
seconds
minimum
Application
instructions varies per
instruction
Program language
Instructions, Ladder Logic and SFC
Program capacity
15872 STEPS
SRAM + Battery
Instructions
32 Basic instructions
197 Application
instructions
X External inputs
X0~X377, octal number
system, 256 points max.
Physical input points
Y External outputs
Y0~Y377, octal number
system, 256 points max.
Total
512 I/O
Physical output points
General
M0~M511, Note 2
M512~M999, Note 3
Latched
M2000~M4095, Note 3
M
Auxiliary relay Special
M1000~M1999
some are latched
Total
4096 bits
Main internal relay
area for general use.
T0~T199, Note 2
T192~T199 for Subroutine
100ms
T250~T255(accumulative),
6 points Note 4
T200~T239, Note 2
10ms
T240~T245(accumulative),
6 points, Note 4
T
Ti
m
er
1ms
T246~T249(accumulative),
4 points, Note 4
Total
256 bits
Contact = ON when
timer reaches preset
value.
C0~C99, Note 2
16-bit count up
C100~C199, Note 3
C200~C219, Note 2
32-bit count
up/down
C220~C234, Note 3
Total
235 bits
C235~C244, 1 phase 1
input, 10 points, Note 3
C246~C249, 1 phase 2
input, 4 points, Note 3
Bit
C
Cou
nter
32bit
high-speed
count up/down
C251~C254, 2 phase 2
input, 4 points, Note 3
Total
18 bits
Contact = ON when
counter reaches
preset value.